Helios KWL 360 W Installation And Operating Instructions Manual

Central ventilation unit
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Helios Ventilatoren
MONTAGE- UND BETRIEBSVORSCHRIFT
INSTALLATION AND OPERATING INSTRUCTIONS
NOTICE DE MONTAGE ET D'UTILISATION
Zentrales Lüftungsgerät
Central ventilation unit
Unité de ventilation centrale
KWL 360 W
KWL 360 W ET
Kompaktes Wandgerät mit Wärmerückgewinnung
und EC-Technik
Compact wall-mounted unit with heat recovery
and EC technology
Centrale murale compacte avec récupération de chaleur
et technologie EC
DE
EN
FR
easy
Controls 3.0

Advertisement

Table of Contents
loading

Summary of Contents for Helios KWL 360 W

  • Page 1 Controls 3.0 Zentrales Lüftungsgerät Central ventilation unit Unité de ventilation centrale KWL 360 W KWL 360 W ET Kompaktes Wandgerät mit Wärmerückgewinnung und EC-Technik Compact wall-mounted unit with heat recovery and EC technology Centrale murale compacte avec récupération de chaleur...
  • Page 2: Table Of Contents

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET INHALTSVERZEICHNIS MONTAGE- UND BETRIEBSVORSCHRIFT KAPITEL 1 SICHERHEIT ................................. SEITE 3 Grundlegende Hinweise ................................. Seite 3 Warnhinweise ..................................Seite 3 Sicherheitshinweise ................................Seite 3 Einsatzbereich ..................................Seite 4 Personalqualifikation ................................Seite 4 KAPITEL 2 GRUNDLEGENDE HINWEISE ............................
  • Page 3 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET DEUTSCH KAPITEL 7 BEDIENUNG ................................SEITE 22 Bedienungsmöglichkeiten ..............................Seite 22 7.1.1 Lokaler Webserver ................................Seite 22 7.1.2 easyControls Cloud-Dienst ..............................Seite 22 7.1.3 Bedienelemente ................................. Seite 22 7.1.4 Gebäudeleittechnik (GLT) ..............................Seite 22 Geräteeinstellungen über easyControls 3.0 .........................
  • Page 4 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET KAPITEL 1 Grundlegende Hinweise Zur Sicherstellung einer einwandfreien Funktion und zur eigenen Sicherheit sind alle nachstehenden Vorschriften genau SICHERHEIT durchzulesen und zu beachten. Die national einschlägigen Normen, Sicherheitsbestimmungen und Vorschriften (z.B.
  • Page 5: Montage- Und Betriebsvorschrift

    Einsatzbereich – Bestimmungsgemäßer Einsatz Das zentrale Lüftungsgerät KWL 360 W/W ET mit Wärmerückgewinnung, ist für die zentrale Be- und Entlüftung von Wohnhäusern und Etagenwohnungen konzipiert. Das Gerät ist zur Förderung normaler oder leicht staubhaltiger (Parti- kelgröße < 10 µm), wenig aggressiver und feuchter Luft, in gemäßigtem Klima und im Bereich seiner Leistungskennlinie geeignet.
  • Page 6: Grundlegende Hinweise

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET KAPITEL 2 Transport Das Gerät ist werkseitig so verpackt, dass es gegen normale Transportbelastungen geschützt ist. Der Transport muss GRUNDLEGENDE sorgfältig durchgeführt werden. HINWEISE Bei Weiterversand, vor allem über längere Distanzen (z.B. Seeweg) ist zu prüfen, ob die Verpackung für Transportart und -weg geeignet ist.
  • Page 7: Vorschriften Und Richtlinien

    Alle Ausführungen der zum Gerät gehörenden Dokumentationen müssen beachtet werden, sonst entfällt die Gewähr- leistung. Gleiches gilt für Haftungsansprüche an den Hersteller. Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht zulässig. Even tuell auftretende Schäden unterliegen nicht der Gewährleistung.
  • Page 8: Geräteübersicht

    Der Wärmebereitstellungsgrad ist von den Faktoren Luftfeuchtigkeit und dem Temperaturunterschied zwischen Außen- und Abluft abhängig. Geräte mit Enthalpie-Wärmetauscher (KWL 360 W ET) gewinnen neben der Wärme auch Feuch- tigkeit aus der Abluft zurück, die den Räumen mit der Zuluft wieder zugeführt wird.
  • Page 9: Technische Daten

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Bei Verwendung eines Heizregisters, muss das Rohrsystem 0,5m vor und nach dem Heizregister mit temperaturbeständigem bzw. nicht brennbarem Rohr versehen werden (z.B. Wickelfalzrohr) Abb. 2 Abluft Abb. KWL 360 W Zuluft ...
  • Page 10: Abmessungen

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Abmessungen Abb. 3 Fortluft Abluft ø160 Zuluft Aussenluft Kugelsiphon ø12 Maße in mm Zubehör Zur Erweiterung des KWL Systems stehen weiteres Zubehör sowie passende Systemkomponenten zur Verfügung. ® Weitere Informationen und Details finden Sie auf HeliosSelect unter www.HeliosSelect.de.
  • Page 11: Einbauhinweise

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET KAPITEL 4 Einbauhinweise 4.1.1 Positionierung MONTAGE Das Gerät ist zur Installation innerhalb der Wohneinheit bzw. des Gebäudes, an der Wand oder zum Einbau in einen Schrank, vorgesehen. Aufgrund der Betriebsgeräusche wird empfohlen, das Gerät in einem Nebenraum (z.B. Wasch- raum, Technikraum oder Abstellraum) zu installieren.
  • Page 12: Gerät Montieren

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Für den Umbau des Gerätes müssen Geräteabdeckung und Geräterückwand getauscht werden. Hierzu wie folgt vor- gehen: Verletzungsgefahr durch Herunterfallen der Gerätetür bzw. der Geräterückwand! WARNUNG Die Gerätetür bzw. -rückwand kann beim Abnehmen herunterfallen und schwere Verletzungen verursachen.
  • Page 13: Kugelsiphon Montieren

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Kugelsiphon montieren Während der Heizperiode kann es durch den Prozess der Wärmerückgewinnung, im Wärmetauscher zur Bildung von Kondensat kommen. Das Kondensat muss frei aus dem Gerät ablaufen können. Hierzu muss der beiliegende Kugelsi- phon (Lieferumfang) in der Bodenwanne des Gerätes montiert werden.
  • Page 14: Lüftungsleitungen Anschließen

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET 6. Kondensatschlauch (Länge max. 1,5 m) an das Entwässerungssystem des Gebäudes anschließen (s. Abb. 17). Abb. 17 Kondensatschlauch DN 12 mm (Gefälle beachten!) 7. Kugelsiphon kontrollieren: – Um die Dichtheit zu gewährleisten, darf der Kugelsiphon bei bauseitiger Montage keinen seitlichen Belastungen durch den Kondensatschlauch ausgesetzt sein! –...
  • Page 15: Anschlussplan

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET 5.1.1 Anschlussplan Abb. 18 Modbus Leitungslänge: maximal 100 m es müssen paarw eise verdrillte Aderpaare verw endet 3x0,5 mm w erden. KWL-VOC eC Sensor* Externes Modbus Art. Nr.: 20247 KWL-BE...
  • Page 16: Verdrahtungsplan

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET 5.1.2 Verdrahtungsplan Abb. 19 MB_A MB_A MB_B MB_B +24V +24V RS_A RS_A RS_B RS_B siehe SS-1433 +24V RS_A +24V RS_A RS_B RS_B +11V1 +24V AN/I D/I1 +24V RM/I D/I2 RM/O...
  • Page 17: Erstinbetriebnahme

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET KAPITEL 6 Erstinbetriebnahme Für die Erstinbetriebnahme muss das Gerät ordnungsgemäß an das Stromnetz angeschlossen bzw. mit dem Stromnetz INBETRIEBNAHME verbunden sein. Anschließend kann der Inbetriebnahmeassistent über den lokalen Webserver oder optional über das Bedienelement KWL-BE Touch (Zubehör) durchgeführt werden.
  • Page 18: Einregulierung

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET > Die Einstellungen für die Konfiguration des Gerätes werden angezeigt. Abb. 22 4. Gerät konfigurieren und auf „Weiter“ klicken. > Die Zusammenfassung der Einstellungen öffnet sich. 5. Einstellungen prüfen und ggf. anpassen.
  • Page 19 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Abb. 23 Abb. 24 Kennlinie KWL 360 W Kennlinie KWL 360 W Zuluft Abluft 10 % â â 10 % â â 20 % ê ê 20 % ê ê...
  • Page 20 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET 5. Die ermittelten Differenzdrücke der Ab- und Fortluftmessung in die Kennlinie des Gerätes für Abluft (s. Abb. 24 und Abb. 26), entsprechend der im Lüftungsprofil hinterlegten Ventilatorleistungen, eintragen (vgl. Abb. 28 und Abb. 29).
  • Page 21 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Ventilatorleistungen ermitteln: 1. Volumenströme aus der Auslegungsberechnung für die drei Lüftungsprofile „Zuhause“, „Unterwegs“ und „Intensiv- lüftung“ in die Kennlinie des Gerätes für Zu- und Abluft eintragen (vgl. Abb. 31). ⓘ Wir empfehlen folgende Werte in den Lüftungsprofilen zu hinterlegen: •...
  • Page 22: Volumenstrommessung Zur Einregulierung Der Anlage (Feinjustierung) Durchführen

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Abb. 33 6.3.3 Volumenstrommessung zur Einregulierung der Anlage (Feinjustierung) durchführen • Volumenströme an allen Ventilen im Zu- und Abluftstrang messen. • Volumenströme jeweils für Zu- und Abluftstränge aufsummieren. • Bei Abweichungen zu den gewünschten Volumenströmen, diese entsprechend durch Erhöhen oder Verringern an- passen.
  • Page 23 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET KAPITEL 7 Bedienungsmöglichkeiten 7.1.1 Lokaler Webserver BEDIENUNG Das Gerät kann über den lokalen Webserver mittels einem Webbrowser, über ein mobiles Endgerät (z.B. Notebook, PC, Tablet, Smartphone) konfiguriert werden. Es ist keine Anmeldung/Registrierung des Gerätes erforderlich.
  • Page 24 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET ZUHAUSE Lüftungsprofil bei Anwesenheit von Personen. Folgende Parameter sind einstellbar: • Ventilatorleistung • Zuluft Hier ist die Solltemperatur für die Zuluft einzustellen. ⓘ     O hne Nachheizung (optional; als Zubehör erhältlich) liegt die maximal erreichbare Solltemperatur 2-3 °C unter der Ablufttemperatur.
  • Page 25 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET 7.2.1.7 Wochenprogramm Abb. 35 • Wochenprogramm ein-/ausschalten • Wochenprogramm erstellen/bearbeiten Durch Klicken auf ein Feld ändert sich das Lüftungsprofil in folgender Reihenfolge (vgl. Abb. 35): Lüftungsprofil „Zuhause“ (1x klicken) Lüftungsprofil „Unterwegs“ (2x klicken) Lüftungsprofil „Intensivlüftung“...
  • Page 26 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET 7.2.4 Einstellungen 7.2.4.1 Sprache Gewünschte Sprache für die Benutzeroberfläche auswählen. 7.2.4.2 Freigabecode Freigabecode ändern. ⓘ Standardmäßig ist der Freigabecode 0000 voreingestellt. 7.2.4.3 Cloud-Dienst Gerät mit dem easyControls Cloud-Dienst verbinden oder Cloud-Dienst trennen. Beim Verbinden mit dem Cloud-Dienst öffnet sich die Startseite zur Anmeldung automatisch.
  • Page 27 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET • Not-Aus/Normalbetrieb (0 V / 24 V) • Intensivlüftung Aus/Ein (0 V / 24 V) • Normalbetrieb / Bypass (0 V / 24 V) • Wochenprogramm Aus / Ein (0 V / 24 V) •...
  • Page 28 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET KAPITEL 8 Gerät warten Das Gerät ist je nach Bedarf, jedoch mindestens einmal im Jahr auf Verschmutzungen und Verunreinigungen zu prüfen WARTUNG UND (Sichtprüfung). SERVICE Lebensgefahr durch elektrischen Schlag! Ein elektrischer Schlag kann zu Tod oder schweren Verletzungen führen.
  • Page 29 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET Die Filter sind als Zubehör erhältlich: Ersatzluftfilter Grobfilter Coarse 65 % (2 Stk.) ELF-KWL 360/4/4 Best.-Nr. 07371 Ersatzluftfilter Feinfilter ePM 1 50 % (1 Stk.) ELF-KWL 360/7 Best.-Nr. 07375 Ersatzluftfilter Aktivkohle ePM 2.5 60 % (1 Stk.) ELF-KWL 360 AK Best.-Nr.
  • Page 30 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET – Nur für Elektrofachkraft Lebensgefahr durch elektrischen Schlag! GEFAHR Ein elektrischer Schlag kann zu Tod oder schweren Verletzungen führen. > Vor Öffnen des Gerätes, ist das Gerät allpolig vom Netz zu trennen.
  • Page 31 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 360 W/W ET...
  • Page 32 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET TABLE OF CONTENTS INSTALLATION AND OPERATING INSTRUCTIONS CHAPTER 1 SAFETY ..................................PAGE 3 Basic information ..................................Page 3 Warning instructions ................................Page 3 Safety instructions .................................. Page 3 Area of application ..................................
  • Page 33 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET ENGLISH CHAPTER 7 OPERATION................................PAGE 22 Operating options ................................. Page 22 7.1.1 Local web server ................................Page 22 7.1.2 easyControls cloud service ..............................Page 22 7.1.3 Control elements ................................Page 22 7.1.4...
  • Page 34: Installation And Operating Instructions

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET CHAPTER 1 Basic information In order to ensure correct operation and for your own safety, please read and observe the following instructions carefully SAFETY before proceeding. Relevant national standards, safety regulations and provisions (e.g. DIN EN VDE 0100) as well as the technical connection conditions of the energy supply company must be observed and applied.
  • Page 35: Area Of Application

    – Intended use The central ventilation unit KWL 360 W/W ET with heat recovery is designed for the central supply and extract venti- lation of residential houses and apartments. The unit is suitable for conveying normal or slightly dusty (particle size <...
  • Page 36: Chapter 2 Basic Information

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET CHAPTER 2 Shipping The delivery is packed ex works in such a way that it is protected against normal transport strain. The shipping must BASIC be carried out carefully.
  • Page 37: Regulations And Guidelines

    All versions of this documentation must be observed, otherwise the warranty shall cease to apply. The same applies to liability claims against the manufacturer. The use of accessory parts which are not recommended or offered by Helios is not permitted. Any possible damages are not covered by the warranty.
  • Page 38: Chapter 3 Product Information

    The heat recovery efficiency depends on the factors of humidity and the temperature difference between intake and extract air. Units with enthalpy heat exchangers (KWL 360 W ET) recover humidity from the extract air in addition to heat, which is returned to the rooms through the supply air.
  • Page 39: Technical Data

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Bei Verwendung eines Heizregisters, muss das Rohrsystem 0,5m vor und nach dem Heizregister mit temperaturbeständigem bzw. nicht brennbarem Rohr versehen werden (z.B. Wickelfalzrohr) Fig. 2 Extract air Abluft Abb.
  • Page 40: Dimensions

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Dimensions Fig. 3 Fortluft Exhaust air Abluft Extract air ø160 Zuluft Intake air Aussenluft Supply air Kugelsiphon Ball siphon ø12 Dimensions in mm Accessories Additional accessories and matching system components are available to expand the KWL system.
  • Page 41: Chapter 4 Installation

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET CHAPTER 4 Installation instructions 4.1.1 Positioning INSTALLATION The unit is designed for installation on the wall inside the residential unit or building or for installation in a cabinet. Due to the operating noise, it is recommended to install the unit in a secondary room (e.g.
  • Page 42: Install Unit

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET The unit cover and rear panel must be replaced to modify the unit. Proceed as follows: Risk of injury due to the unit door or rear panel falling down! WARNING The unit door or rear panel can fall down when removing and cause serious injuries.
  • Page 43: Install Ball Siphon

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Install ball siphon During heating periods, condensate may form in the heat exchanger due to the heat recovery process. The condensa- te must be able to drain freely from the unit. The provided ball siphon (scope of delivery) must be installed in the base tray of the unit for this purpose.
  • Page 44: Connect Ventilation Ducts

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET 6. Connect condensate hose (length max. 1.5 m) to the building drainage system (see Fig. 17). Fig. 17 Condensate hose DN 12 mm (note gradient!) 7. The ball siphon must be inspected: –...
  • Page 45: Connection Diagram

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET 5.1.1 Connection diagram Fig. 18 Modbus cable length: maximum 100 m 3x0,5 mm tw isted pairs of w ires must be used. KWL-VOC eC Remote Sensor* monitoring art. nr.: 20247...
  • Page 46: Wiring Diagram

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET 5.1.2 Wiring diagram Fig. 19 MB_A MB_A MB_B MB_B +24V +24V RS_A RS_A RS_B RS_B SS-1433 +24V RS_A +24V RS_A RS_B RS_B +11V1 +24V AN/I D/I1 +24V RM/I...
  • Page 47: Chapter 6 Commissioning

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET CHAPTER 6 Initial commissioning The unit must be properly connected or linked to the mains power supply for the initial commissioning. The commissio- COMMISSIONING ning assistant can then run via the local web server or optionally via the control element KWL-BE Touch (accessories).
  • Page 48: Adjustment

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET > The settings for unit configuration are displayed. Fig. 23 4. Configure unit and click “Next”. > The settings summary page will open up. 5. Check settings and adjust if necessary.
  • Page 49 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Fig. 24 Fig. 25 Characteristic curve KWL 360 W Characteristic curve KWL 360 W Supply air Extract air 10 % â â 10 % â â 20 % ê...
  • Page 50 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET 4. Enter the determined differential pressures from the supply and intake air measurement in the unit characteristic curve for supply air (see Fig. 24 and Fig. 26) according to the fan outputs saved in the ventilation profile (cf. Fig. 29 and Fig.
  • Page 51 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Determine fan powers: 1. Enter the flow rates from the design calculation for the three ventilation profiles “At home”, “Away” and “Boost” in the unit characteristic curve for supply and extract air (cf. Fig. 32).
  • Page 52: Perform Flow Rate Measurement For Adjusting The System (Fine Adjustment)

    Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Fig. 34 6.3.3 Perform flow rate measurement for adjusting the system (fine adjustment) • Measure the flow rates at all valves in the supply and extract air ducts.
  • Page 53 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET CHAPTER 7 Operating options 7.1.1 Local web server OPERATION The unit can be configured via the local web server using a web browser, via a mobile end device (e.g. notebook, PC, tablet, smartphone).
  • Page 54 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET AT HOME Ventilation profile in the presence of persons. The following parameters can be adjusted: • Fan power • Supply air The target supply air temperature is adjusted here.
  • Page 55 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET 7.2.1.7 Weekly programme Fig. 45 • Activate/deactivate weekly programme • Create/edit weekly programme The ventilation profile changes in the following order by clicking on a field (cf. Fig. 45): Ventilation profile “At home”...
  • Page 56 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET 7.2.4 Settings 7.2.4.1 Language Select the desired language for the user interface. 7.2.4.2 Release code Change release code. ⓘ The release code is pre-set to 0000 as standard.
  • Page 57 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET • Normal mode / Bypass (0 V / 24 V) • Weekly programme Off / On (0 V / 24 V) • Configurable input Off / On (0 V / 24 V) ⓘ...
  • Page 58 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET CHAPTER 8 Unit maintenance The unit must be checked for contamination and dirt (visual inspection) as needed or at least every year. SERVICE AND Danger to life due to electric shock MAINTENANCE An electric shock can result in death or serious injuries.
  • Page 59 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Heat exchanger maintenance and cleaning 8.3.1 Heat exchanger maintenance The heat exchanger must be checked as needed or at least every year for contamination and dirt (visual inspection) and, if necessary, cleaned, see chapter 8.3.2 „Heat exchanger cleaning“, page 28.
  • Page 60 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET Risk of burns due to hot surfaces! WARNING Hot surfaces can cause serious burns. > Allow unit to cool down for at least 5 minutes or wait until the fans are turned off.
  • Page 61 Installation and Operating Instructions Central ventilation unit – KWL 360 W/W ET...
  • Page 62 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET SOMMAIRE NOTICE DE MONTAGE ET D‘UTILISATION CHAPITRE 1 SÉCURITÉ ................................. PAGE 3 Informations générales ................................Page 3 Consignes de sécurité ................................Page 3 Consignes de sécurité ................................Page 3 Domaines d‘utilisation ................................
  • Page 63: Notice De Montage Et D'utilisation

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET FRANÇAIS CHAPITRE 7 COMMANDE ................................PAGE 22 Possibilités de commande ..............................Page 22 7.1.1 Serveur web local ................................Page 22 7.1.2 Service Cloud easyControls .............................. Page 22 7.1.3...
  • Page 64: Informations Générales

    Filet à cheveux Le filet à cheveux empêche les longs cheveux de se coincer dans les pièces mobiles. Pour le fonctionnement, le raccordement et l’utilisation, contacter Helios en cas de doutes. Des informations supplémentaires sont consultables dans les normes et textes de loi.
  • Page 65: Domaines D'utilisation

    Domaines d‘utilisation – Usage prévu La centrale KWL 360 W/W ET avec récupération de chaleur est conçue pour la ventilation centrale des bâtiments résidentiels et des appartements. L‘appareil est adapté au transport d‘air normal ou légèrement pollué (taille des parti- cules <...
  • Page 66: Transport

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET CHAPITRE 2 Transport L’appareil est emballé en usine et est protégé des dégâts de transport courants. Transporter l’appareil avec précautions. INFORMATIONS En cas de transport ultérieur, en particulier sur de longues distances (par exemple par mer), il faut vérifier si l‘emballage GÉNÉRALES...
  • Page 67: Normes - Règlementations

    Si toutes les consignes indiquées dans cette notice ne sont pas correctement respectées, la garantie s’annule. Idem pour les garanties constructeur Helios. L’utilisation d’accessoires, non fournis, non conseillés ou non proposés par Helios, est interdite. Tous changements ou transformations effectués sur l’appareil sont interdits, altèrent sa conformité...
  • Page 68: Vue D'ensemble De L'appareil

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET CHAPITRE 3 Vue d‘ensemble de l‘appareil INFORMATIONS Fig. 1 SUR LE PRODUIT              ...
  • Page 69: Données Techniques

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Bei Verwendung eines Heizregisters, muss das Rohrsystem 0,5m vor und nach dem Heizregister mit temperaturbeständigem bzw. nicht brennbarem Rohr versehen werden (z.B. Wickelfalzrohr) Fig. 2 air extrait Abluft Abb.
  • Page 70: Dimensions

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Dimensions Fig. 3 Fortluft air rejeté Abluft air extrait ø160 Zuluft air extérieur Aussenluft air soufflé Kugelsiphon Siphon à boule ø12 Dimensions en mm Accessoires Des accessoires supplémentaires et des composants appropriés sont disponibles en complément du système KWL ®...
  • Page 71: Instructions D'installation

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET CHAPITRE 4 Instructions d‘installation 4.1.1 Positionnement MONTAGE L‘appareil est destiné à être installé au mur ou dans une armoire à l‘intérieur de l‘appartement ou du bâtiment. En raison du bruit de fonctionnement, il est recommandé...
  • Page 72: Montage De L'appareil

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Pour démonter l‘appareil, les panneaux avant et arrière doivent être intervertis. Pour ce faire, procéder comme suit : Risque de blessure dû à la chute de la porte de l‘appareil ou du panneau arrière ! AVERTISSEMENT La porte ou le panneau arrière de l‘appareil peuvent tomber lorsqu‘ils sont retirés et provoquer des blessures...
  • Page 73: Montage Du Siphon À Boule

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Montage du siphon à boule Pendant la période de chauffe, des condensats peuvent se former dans l‘échangeur à contre-courant en raison du processus de récupération de la chaleur. Le condensat doit pouvoir s‘écouler librement de l‘appareil. Le siphon à boule (inclus dans la livraison) doit être monté...
  • Page 74: Raccordement Des Conduits De Ventilation

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET 6. Raccorder le tube des condensats (longueur max. 1,5 m) au système d’évacuation des eaux usées du bâtiment (à un siphon) (voir Fig. 17). Fig. 17 Tubes des condensats DN 12 mm (doit être en pente !)
  • Page 75: Schéma De Raccordement

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET 5.1.1 Schéma de raccordement Fig. 18 Longueur du câble Modbus : 100 m maximum 3x0,5 mm Il faut utiliser des paires de fils torsadés. KWL-VOC eC Surveillance à...
  • Page 76: Schéma De Câblage

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET 5.1.2 Schéma de câblage Fig. 19 MB_A MB_A MB_B MB_B +24V +24V RS_A RS_A RS_B RS_B voir SS-1433 +24V RS_A +24V RS_A RS_B RS_B +11V1 +24V...
  • Page 77: Première Mise En Service

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET CHAPITRE 6 Première mise en service Pour la première mise en service, l‘appareil doit être correctement raccordé au réseau électrique ou branché au secteur. MISE EN SERVICE L‘assistant de mise en service peut ensuite être mis en place via le serveur web local ou, en option, via la commande...
  • Page 78: Paramétrages

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET > Les paramètres de configuration de l‘appareil s‘affichent. Fig. 22 4. Configurer l‘appareil et cliquer sur „Suivant“. > Le récapitulatif des paramètres s‘ouvre. 5. Vérifier les paramètres et les ajuster si nécessaire.
  • Page 79 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Fig. 23 Fig. 24 Courbe caractéristique KWL 360 W Courbe caractéristique KWL 360 W Air soufflé Air extrait 10 % â â 10 % â â...
  • Page 80 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET 4. Entrer les pressions différentielles déterminées de la mesure de l‘air soufflé et extérieur dans la courbe caractéristique de l‘appareil pour l‘air soufflé (voir Fig. 23 et Fig. 25), en fonction des performances du ventilateur enregistrées dans le profil de ventilation (voir Fig.
  • Page 81 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Déterminer les performances du ventilateur : 1. Saisir les débits volumiques issus du l‘étude pour les trois profils de ventilation „Présent“, „Absent“ et „Forcé“ dans la courbe caractéristique de l‘appareil pour l‘air soufflé et extrait (voir Fig. 31).
  • Page 82: Réglage Par Mesure Du Débit Volumique (Réglage Fin)

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Fig. 33 6.3.3 Réglage par mesure du débit volumique (réglage fin) • Mesurer les débits sur toutes les bouches de soufflage et d‘extraction d‘air. • Additionner les débits de soufflage et d‘extraction d‘air.
  • Page 83 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET CHAPITRE 7 Possibilités de commande 7.1.1 Serveur web local COMMANDE L‘appareil peut être configuré via le serveur web local à l‘aide d‘un navigateur web, via un appareil mobile (par exemple un ordinateur portable, un PC, une tablette, un smartphone).
  • Page 84 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET PRÉSENT Profil de ventilation en présence de personnes. Les paramètres suivants peuvent être définis : • Vitesse ventilateur • Définir température air neuf Ici, vous fixez la température de consigne pour l‘air d‘alimentation.
  • Page 85 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET 7.2.1.7 Programme hebdomadaire Fig. 35 • Activer/désactiver le programme hebdomadaire • Créer/modifier le programme hebdomadaire En cliquant sur un champ, le profil de ventilation change dans l‘ordre suivant (voir Fig. 35) Profil de ventilation „Présent“...
  • Page 86 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET 7.2.4 Réglages 7.2.4.1 Langue Sélectionner la langue souhaitée pour l‘interface utilisateur. 7.2.4.2 Code d‘accès Changer le code d‘accès. ⓘ Le code d‘accès 0000 est préréglé par défaut.
  • Page 87 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET • Ventilation intensive arrêt/marche (0 V / 24 V) • Fonctionnement normal / Bypass (0 V / 24 V) • Programme hebdomadaire arrêt/marche (0 V / 24 V) •...
  • Page 88 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET CHAPITRE 8 Entretien de l‘appareil L‘appareil doit être contrôlé en fonction des besoins, mais au moins une fois par an (inspection visuelle). ENTRETIEN ET Danger de mort par électrocution ! MAINTENANCE En choc électrique peut entraîner la mort ou des blessures graves.
  • Page 89 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Entretien et nettoyage de l‘échangeur à contre-courant 8.3.1 Entretien de l‘échangeur à contre-courant L‘échangeur à contre-courant doit être inspecté selon les besoins ou au moins une fois par an pour détecter les salis- sures et l‘encrassement (inspection visuelle) et être nettoyé...
  • Page 90 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET Risque de brûlures en raison de surfaces chaudes ! AVERTISSEMENT Les surfaces chaudes peuvent causer de graves brûlures. > Laisser refroidir la centrale 5 min et attendre l’arrêt complet des ventilateurs.
  • Page 91 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 360 W/W ET...
  • Page 92 CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd. · 5 Crown Gate · Wyncolls Road · Severalls Industrial Park · Colchester · HELIOS Ventilatoren · Postfach 854 · Siemensstraße 15 · 6023 Innsbruck...