Helios Ventilatoren
MONTAGE- UND BETRIEBSVORSCHRIFT
INSTALLATION AND OPERATING INSTRUCTIONS
NOTICE DE MONTAGE ET D'UTILISATION
Zentrales Lüftungsgerät
Central ventilation unit
Unité de ventilation centrale
KWL 220 D
KWL 340 D
Kompaktes Deckengerät mit Wärmerückgewinnung
und EC-Technik
Compact ceiling-mounted unit with heat recovery
and EC technology
Centrale murale compacte avec récupération de chaleur
et technologie EC
DE
EN
FR
easy
Controls 3.0

Advertisement

Table of Contents
loading

Summary of Contents for Helios KWL 220 D

  • Page 1 NOTICE DE MONTAGE ET D’UTILISATION easy Controls 3.0 Zentrales Lüftungsgerät Central ventilation unit Unité de ventilation centrale KWL 220 D KWL 340 D Kompaktes Deckengerät mit Wärmerückgewinnung und EC-Technik Compact ceiling-mounted unit with heat recovery and EC technology Centrale murale compacte avec récupération de chaleur...
  • Page 2: Table Of Contents

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D INHALTSVERZEICHNIS MONTAGE- UND BETRIEBSVORSCHRIFT KAPITEL 1 SICHERHEIT ................................. SEITE 3 Grundlegende Hinweise ................................. Seite 3 Warnhinweise ..................................Seite 3 Sicherheitshinweise ................................Seite 3 Einsatzbereich ..................................Seite 4 Personalqualifikation ................................Seite 4 KAPITEL 2 GRUNDLEGENDE HINWEISE ............................
  • Page 3 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D DEUTSCH KAPITEL 7 BEDIENUNG ................................SEITE 28 Bedienungsmöglichkeiten ..............................Seite 28 7.1.1 Lokaler Webserver ................................Seite 28 7.1.2 easyControls Cloud-Dienst ..............................Seite 28 7.1.3 Bedienelemente ................................. Seite 28 7.1.4 Gebäudeleittechnik (GLT) ..............................Seite 28 Geräteeinstellungen über easyControls 3.0 .........................
  • Page 4 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D KAPITEL 1 Grundlegende Hinweise Zur Sicherstellung einer einwandfreien Funktion und zur eigenen Sicherheit sind alle nachstehenden Vorschriften genau SICHERHEIT durchzulesen und zu beachten. Die national einschlägigen Normen, Sicherheitsbestimmungen und Vorschriften (z.B. DIN EN VDE 0100) sowie die Technischen Anschlussbedienungen des örtlichen Energieversorgungsunternehmens sind unbedingt zu beachten und anzuwenden.
  • Page 5: Montage- Und Betriebsvorschrift

    Stillstandzeiten, starke Verschmutzung (z.B. fetthaltige Luft), übermäßige Beanspruchung durch klimatische, tech- nische oder elektronische Einflüsse, geeignet. Gleiches gilt für die mobile Verwendung des Gerätes (Fahr-, Flugzeuge, Schiffe, usw.). Ein Einsatz unter diesen Bedingungen ist nur mit Einsatzfreigabe seitens Helios möglich, da die Serien- ausführung hierfür nicht geeignet ist.
  • Page 6: Grundlegende Hinweise

    Geräuschpegel, sind glattwandige Rohre zu verwenden. Für die Hauptleitungen (Außenluft, Fortluft, Zuluft und Abluft) ist der Rohrdurchmesser DN 125 mm (KWL 220 D) bzw. DN 160 mm (KWL 340 D) vorzusehen. Für Stichlei- tungen kann der Durchmesser entsprechend reduziert werden. Die Zuluft ist den Wohn- und Schlafräumen zuzuführen, die Abluft in den Nutzräumen abzuführen.
  • Page 7: Vorschriften Und Richtlinien

    Alle Ausführungen der zum Gerät gehörenden Dokumentationen müssen beachtet werden, sonst entfällt die Gewähr- leistung. Gleiches gilt für Haftungsansprüche an den Hersteller. Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht zulässig. Even tuell auftretende Schäden unterliegen nicht der Gewährleistung.
  • Page 8: Geräteübersicht

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D KAPITEL 3 Geräteübersicht PRODUKT- Abb. 1  INFORMATION                  Zuluftventilator Abdeckung Klemmenkasten Gehäuse      ...
  • Page 9: Technische Daten

    T1 Ablufttemperaturfühler IP 160/2000 (Zubehör KWL 340 D) Rohrverbinder kurz Ø125/160 T2 Fortlufttemperaturfühler     RVBD 125 K (Zubehör KWL 220 D) T3 Außenlufttemperaturfühler RVBD 160 K (Zubehör KWL 340 D) T4 Zulufttemperaturfühler T6 Lufttemperatur-Kanalfühler / KWL-LTK (Zubehör) Technische Daten...
  • Page 10: Abmessungen

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D Abmessungen Abb. 3 KWL 220 D R 170 193 1141 ø125 Muffe ø12 Kugel- siphon Zuluft Außenluft Fortluft Abluft Ansicht von oben * Kugelsiphon an Geräte- Unterseite / an Wand 1175 Maße in mm...
  • Page 11: Schalldaten

    Max. Kennlinie Punkte 5-8 Punkte 9-12 Punkte 9-12 Max Kennlinie Max Kennlinie Volumenstrom m³/h Volumenstrom m³/h Volumenstrom Volumenstrom Volumenstrom m³/h umenstrom m³/h Schallleistung Gehäuseabstrahlung KWL 220 D Ventilator- Volumen- Summen- Schalldruck- Druck Punkt leistung strom pegel L pegel L [Pa]...
  • Page 12: Schallleistung Zuluft

    Max. Kennlinie Punkte 5-8 Punkte 5-8 Punkte 9-12 Punkte 9-1 Max Kennlinie Max Kenn Volumenstrom m³/h Volumenstrom m³/h Volumenstrom Volumenstrom umenstrom m³/h Volumenstrom m³/h Schallleistung Zuluft KWL 220 D Ventilator- Volumen- Summen- Druck Punkt leistung strom pegel [Pa] [Hz] [Hz] [Hz]...
  • Page 13: Schallleistung Abluft

    Max. Kennlinie Punkte 5-8 Punkte 5 Punkte 9-12 Punkte 9 Max Kennlinie Max Ken Volumenstrom m³/h Volumenstrom m³/h Volumenstrom Volumenstrom Volumenstrom m³/h umenstrom m³/h Schallleistung Abluft KWL 220 D Ventilator- Volumen- Summen- Druck Punkt leistung strom pegel [Pa] [Hz] [Hz] [Hz]...
  • Page 14: Schallleistung Fortluft

    Max. Kennlinie Punkte 5-8 Punkte 5- Punkte 9-12 Punkte 9- Max Kennlinie Max Kenn Volumenstrom m³/h Volumenstrom m³/h Volumenstrom Volumenstrom lumenstrom m³/h Volumenstrom m³/h Schallleistung Fortluft KWL 220 D Ventilator- Volumen- Summen- Druck Punkt leistung strom pegel [Pa] [Hz] [Hz] [Hz]...
  • Page 15: Schallleistung Außenluft

    Max. Kennlinie Punkte 5-8 Punkte 5-8 Punkte 9-12 Punkte 9-12 Max Kennlinie Max Kennlinie Volumenstrom m³/h Volumenstrom m³/h Volumenstrom Volumenstrom menstrom m³/h Volumenstrom m³/h Schallleistung Außenluft KWL 220 D Ventilator- Volumen- Summen- Druck Punkt leistung strom pegel [Pa] [Hz] [Hz] [Hz]...
  • Page 16: Positionierung

    Für Wartungs- und Installationsarbeiten muss das Gerät bzw. der Klemmenkasten frei zugänglich sein. Die erforder- lichen Mindestabstände zu Wand und Decke sind zu beachten und einzuhalten (s. Abb. 22). Abb. 22 KWL 220 D KWL 340 D Maße in mm 1.
  • Page 17: Kugelsiphon Montieren

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D Die Blechwannen verhindern in diesem Bereich die Ansammlung von Kondensat und sind zwingend auf ihre korrekte Lage zu kontrollieren (vgl. Abb. 23 und Abb. 24). Abb. 23 Abb. 24 2. Montagewinkel mit Schwingungsdämpfern (4x; im Lieferumfang enthalten) mit Blechleitschrauben an den unteren Seitenwänden befestigen (s.
  • Page 18 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 3. Verriegelungsteil bis zum Anschlag einstecken (s. Abb. 29). 4. Anschließend den Kondensatschlauch (DN 12 mm; nicht im Lieferumfang enthalten) in den Schlauchverbinder des Siphon-Gehäuses einstecken und von Hand festschrauben (s. Abb. 30). Abb.
  • Page 19: Variante 2: Montage An Der Wand

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 4.3.2 Variante 2: Montage an der Wand Verletzungsgefahr durch Herunterfallen der Gerätetür! WARNUNG Die Gerätetür kann beim Abnehmen herunterfallen und schwere Verletzungen verursachen. > Sicherheitsschuhe tragen. > Gerätetür vorsichtig, mit beiden Händen, abnehmen. 1.
  • Page 20: Lüftungsleitungen Anschließen

    Lüftungsleitungen anschließen Das Gerät ist mit vier Muffen (Ø 125 mm (KWL 220 D) bzw. Ø 160 mm (KWL 340 D)) für den Anschluss an das Rohrsys- tem ausgerüstet. Die Lüftungsleitungen müssen fest und dicht an die Muffen angeschlossen sein. Hierzu sind die Rohr- anschluss-Verbinder RVBD 125 K (Zubehör) für KWL 220 D bzw.
  • Page 21: Anschlussplan

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 5.1.1 Anschlussplan Abb. 44 KWL-VOC eC Externes Modbus Sensor* Art. Nr.: 20247 KWL-BE Touch 2x2x0,5 mm A+ B- Art. Nr.: 20245 ws KWL-FTF eC 2x2x0,5 mm 2x2x0,5 mm Sensor* Art. Nr.: 20249 KWL-BE Anschlussbox Touch...
  • Page 22: Verdrahtungsplan

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 5.1.2 Verdrahtungsplan Abb. 45 MB_A MB_A MB_B MB_B +24V +24V RS_A RS_A RS_B RS_B siehe SS-1433 +24V RS_A +24V RS_A RS_B RS_B +11V1 +24V AN/I D/I1 Elektroverteilung +24V RM/I D/I2 RM/O Basic Platine gb-gn gb-gn...
  • Page 23: Erstinbetriebnahme

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D KAPITEL 6 Erstinbetriebnahme Für die Erstinbetriebnahme muss das Gerät ordnungsgemäß an das Stromnetz angeschlossen bzw. mit dem Stromnetz INBETRIEBNAHME verbunden sein. Anschließend kann der Inbetriebnahmeassistent über den lokalen Webserver oder optional über das Bedienelement KWL-BE Touch (Zubehör) durchgeführt werden.
  • Page 24: Einregulierung

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D Abb. 48 4. Gerät konfigurieren und auf „Weiter“ klicken. > Die Zusammenfassung der Einstellungen öffnet sich. 5. Einstellungen prüfen und ggf. anpassen. 6. „Zurück“ klicken, um die Einstellungen anzupassen. 7. „Fertig“ klicken, um die Erstinbetriebnahme abzuschließen. Einregulierung ⓘ...
  • Page 25 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D Abb. 49 Abb. 50 Kennlinie KWL 220 D Kennlinie KWL 220 D Zuluft Abluft 10 % â 10 % â 20 % ê 20 % ê 30 % ô 30 % ô...
  • Page 26 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 2. Über die Software easyControls 3.0 oder das Bedienelement KWL-BE Touch für die Ventilatorleistungen folgende Wer- te im jeweiligen Lüftungsprofil hinterlegen: Unterwegs: 30 % / Zuhause: 50 % / Intensivlüftung: 80 % (vgl. Abb. 54). 3.
  • Page 27 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D Ventilatorleistungen ermitteln: 1. Volumenströme aus der Auslegungsberechnung für die drei Lüftungsprofile „Zuhause“, „Unterwegs“ und „Intensiv- lüftung“ in die Kennlinie des Gerätes für Zu- und Abluft eintragen (vgl. Abb. 57). ⓘ Wir empfehlen folgende Werte in den Lüftungsprofilen zu hinterlegen: •...
  • Page 28: Volumenstrommessung Zur Einregulierung Der Anlage (Feinjustierung) Durchführen

    Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 5. Unter „Ventilatoreinstellung“ die Ventilatorleistungen für Zu- und Abluft gemäß der ermittelten Werte für die Nenn- lüftung eintragen (vgl. Abb. 59). Abb. 59 6.3.3 Volumenstrommessung zur Einregulierung der Anlage (Feinjustierung) durchführen •...
  • Page 29 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D KAPITEL 7 Bedienungsmöglichkeiten 7.1.1 Lokaler Webserver BEDIENUNG Das Gerät kann über den lokalen Webserver mittels einem Webbrowser, über ein mobiles Endgerät (z.B. Notebook, PC, Tablet, Smartphone) konfiguriert werden. Es ist keine Anmeldung/Registrierung des Gerätes erforderlich. Lokalen Webserver einrichten: 1.
  • Page 30 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D ZUHAUSE Lüftungsprofil bei Anwesenheit von Personen. Folgende Parameter sind einstellbar: • Ventilatorleistung • Zuluft Hier ist die Solltemperatur für die Zuluft einzustellen. ⓘ     O hne Nachheizung (optional; als Zubehör erhältlich) liegt die maximal erreichbare Solltemperatur 2-3 °C unter der Ablufttemperatur.
  • Page 31 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 7.2.1.7 Wochenprogramm Abb. 67 • Wochenprogramm ein-/ausschalten • Wochenprogramm erstellen/bearbeiten Durch Klicken auf ein Feld ändert sich das Lüftungsprofil in folgender Reihenfolge (vgl. Abb. 67): Lüftungsprofil „Zuhause“ (1x klicken) Lüftungsprofil „Unterwegs“ (2x klicken) Lüftungsprofil „Intensivlüftung“...
  • Page 32 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 7.2.4 Einstellungen 7.2.4.1 Sprache Gewünschte Sprache für die Benutzeroberfläche auswählen. 7.2.4.2 Freigabecode Freigabecode ändern. ⓘ Standardmäßig ist der Freigabecode 0000 voreingestellt. 7.2.4.3 Cloud-Dienst Gerät mit dem easyControls Cloud-Dienst verbinden oder Cloud-Dienst trennen. Beim Verbinden mit dem Cloud-Dienst öffnet sich die Startseite zur Anmeldung automatisch.
  • Page 33 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D • Not-Aus/Normalbetrieb (0 V / 24 V) • Intensivlüftung Aus/Ein (0 V / 24 V) • Normalbetrieb / Bypass (0 V / 24 V) • Wochenprogramm Aus / Ein (0 V / 24 V) •...
  • Page 34 Das Gerät ist außen- und abluftseitig serienmäßig mit Filtern ISO Coarse 75 % ausgestattet. Die Filter sind als Zubehör erhältlich: Ersatzluftfilter Grobfilter Coarse 75 % (2 Stk.) ELF-KWL 220 D/4/4 Best.-Nr. 09638 Ersatzluftfilter Fein-/Pollenfilter ePM1 50% (1 Stk.) ELF-KWL 220 D/7 Best.-Nr.
  • Page 35 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D Aktivkohlefilter (anstatt F7 Filter) (1 Stk.) ELF-KWL 220 AK Best.-Nr. 03050 Aktivkohlefilter (anstatt F7 Filter) (1 Stk.) ELF-KWL 340 AK Best.-Nr. 03051 Die Filter können unter www.Ersatzluftfilter.de bestellt werden. Wärmetauscher warten und reinigen 8.3.1 Wärmetauscher warten Der Wärmetauscher ist je nach Bedarf oder mindestens einmal jährlich auf Verunreinigungen und Verschmutzungen zu prüfen (Sichtprüfung) und ggf.
  • Page 36 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D 2. Mit einer Gießkanne etwas Wasser in die Kondensatwanne gießen. 3. Prüfen, ob das Wasser über den Kondensatschlauch abläuft und den Kondensatablauf ggf. reinigen. Blechwanne warten Die Blechwannen sind je nach Bedarf jedoch mindestens alle 6 Monate auf ihre Funktion zu prüfen und ggf. zu reinigen. Um die Ansaugung von Kondensat durch die Ventilatoren zu vermeiden, sind im Gerät unter der linken und rechten Motoreinheit Blechwannen montiert.
  • Page 37 Montage- und Betriebsvorschrift Zentrales Lüftungsgerät – KWL 220/340 D...
  • Page 38 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D TABLE OF CONTENTS INSTALLATION AND OPERATING INSTRUCTIONS CHAPTER 1 SAFETY ..................................PAGE 3 Basic information ..................................Page 3 Warning instructions ................................Page 3 Safety instructions .................................. Page 3 Area of application .................................. Page 4 Personnel qualification ................................
  • Page 39 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D ENGLISH CHAPTER 7 OPERATION ................................PAGE 28 Operating options ................................. Page 28 7.1.1 Local web server ................................Page 28 7.1.2 easyControls cloud service ..............................Page 28 7.1.3 Control elements ................................Page 28 7.1.4 Building control system ..............................
  • Page 40: Installation And Operating Instructions

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D CHAPTER 1 Basic information In order to ensure correct operation and for your own safety, please read and observe the following instructions carefully SAFETY before proceeding. Relevant national standards, safety regulations and provisions (e.g. DIN EN VDE 0100) as well as the technical connection conditions of the energy supply company must be observed and applied.
  • Page 41: Area Of Application

    • The unit may only be opened by an authorised electrician and instructed end users. • If the unit network cable is damaged, it must be replaced by the Helios custo- mer service team or a qualified electrician. Area of application –...
  • Page 42: Chapter 2 Basic Infromation

    Use smooth ducts to avoid dirt deposits, high pressure loss and loud noises. The duct diameter DN 125 mm (KWL 220 D) or DN 160 mm (KWL 340 D) must be provided for the main lines (intake air, exhaust air, supply air, extract air).
  • Page 43: Regulations And Guidelines

    All versions of this documentation must be observed, otherwise the warranty shall cease to apply. The same applies to liability claims against the manufacturer. The use of accessory parts which are not recommended or offered by Helios is not permitted. Any possible damages are not covered by the warranty.
  • Page 44: Chapter 3 Product Information

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D CHAPTER 3 Unit overview PRODUCT Fig. 1  INFORMATION                  Supply air fan Terminal box cover Casing  ...
  • Page 45: Technical Data

    IP 160/2000 (accessories KWL 340 D) Short duct connector Ø125/160 T2 Exhaust air temperature sensor     RVBD 125 K (accessories KWL 220 D) T3 Intake air temperature sensor RVBD 160 K (accessories KWL 340 D) T4 Supply air temperature sensor T6 Air temperature duct sensor / KWL-LTK (access.)
  • Page 46: Dimensions

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D Dimensions Fig. 3 KWL 220 D R 170 193 1141 ø125 Sleeve Muffe ø12 Kugel- Ball siphon siphon Zuluft Supply air Außenluft Intake air Fortluft Exhaust air Extract air...
  • Page 47: Sound Data

    Punkte 9-12 Max Kennlinie Max Kennlinie Volumenstrom m³/h Volumenstrom m³/h Flow rate Flow rate Volumenstrom m³/h umenstrom m³/h Sound power level Casing-radiated KWL 220 D Sum level Sound pres- Fan power Flow rate Press. Point sure level L [Pa] [Hz]...
  • Page 48: Sound Power Level Supply Air

    Punkte 9-12 Punkte 9-1 Max Kennlinie Max Kenn Volumenstrom m³/h Volumenstrom m³/h Flow rate Flow rate umenstrom m³/h Volumenstrom m³/h Sound power level Supply air KWL 220 D Fan power Flow rate Press. Sum level Point [Pa] [Hz] [Hz] [Hz]...
  • Page 49: Sound Power Level Extract Air

    Punkte 9-12 Punkte 9 Max Kennlinie Max Ken Volumenstrom m³/h Volumenstrom m³/h Flow rate Flow rate Volumenstrom m³/h umenstrom m³/h Sound power level Extract air KWL 220 D Fan power Flow rate Press. Sum level Point [Pa] [Hz] [Hz] [Hz]...
  • Page 50: Sound Power Level Exhaust Air

    Punkte 9-12 Punkte 9- Max Kennlinie Max Kenn Volumenstrom m³/h Volumenstrom m³/h Flow rate Flow rate lumenstrom m³/h Volumenstrom m³/h Sound power level Exhaust air KWL 220 D Fan power Flow rate Press. Sum level Point [Pa] [Hz] [Hz] [Hz]...
  • Page 51: Sound Power Level Intake Air

    Punkte 9-12 Punkte 9-12 Max Kennlinie Max Kennlinie Volumenstrom m³/h Volumenstrom m³/h Flow rate Flow rate menstrom m³/h Volumenstrom m³/h Sound power level Intake air KWL 220 D Fan power Flow rate Press. Sum level Point [Pa] [Hz] [Hz] [Hz]...
  • Page 52: Chapter 4 Installation

    The unit and terminal box must be freely accessible for maintenance and installation work. The following minimum clearances to the wall and ceiling must be observed and adhered to (see Fig. 22). Fig. 22 KWL 220 D KWL 340 D Dimensions in mm 1.
  • Page 53: Install Ball Siphon

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D The metal trays prevent the accumulation of condensate in this area and they must be checked for correct positioning (cf. Fig. 23 and Fig. 24). Fig. 23 Fig. 24 2.
  • Page 54 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 3. Insert locking part and insert up to stop (Fig. 29). 4. Then insert the condensate hose (DN 12 mm; not included in delivery) in the hose connector on the siphon casing and tighten by hand (Fig.
  • Page 55: Variant 2: Installation On Wall

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 4.3.2 Variant 2: Installation on wall Risk of injury due to the unit door falling downetür! WARNING The unit door can fall down when removing and cause serious injuries. >...
  • Page 56: Connect Ventilation Ducts

    Connect ventilation ducts The unit is equipped with four spigots (Ø 125 mm (KWL 220 D) or Ø 160 mm (KWL 340 D)) for connection to the duct system. The ventilation ducts must be connected firmly and tightly to the spigots. Duct connectors RVBD 125 K (acces- sories) for KWL 220 D or RVBD 160 K (accessories) for KWL 340 D must be used in this respect.
  • Page 57: Connection Diagram

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 5.1.1 Connection diagram Fig. 44 Modbus cable length: maximum 100 m tw isted pairs of w ires must be used. KWL-VOC eC Rem ote Sensor* monitoring art. nr.: 20247 Modbus RTU KWL-BE Touch...
  • Page 58: Wiring Diagram

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 5.1.2 Wiring diagram Fig. 45 MB_A MB_A MB_B MB_B +24V +24V RS_A RS_A RS_B RS_B SS-1433 +24V RS_A +24V RS_A RS_B RS_B +11V1 +24V AN/I D/I1 +24V RM/I Distribution board D/I2 RM/O Motherboard...
  • Page 59: Chapter 6 Commissioning

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D CHAPTER 6 Initial commissioning The unit must be properly connected or linked to the mains power supply for the initial commissioning. The commissio- COMMISSIONING ning assistant can then run via the local web server or optionally via the control element KWL-BE Touch (accessories). •...
  • Page 60: Adjustment

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D Fig. 48 4. Configure unit and click “Next”. > The settings summary page will open up. 5. Check settings and adjust if necessary. 6. Click “Back” to adjust the settings. 7.
  • Page 61 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D Fig. 50 Fig. 51 Characteristic curve KWL 220 D Characteristic curve KWL 220 D Extract air Supply air 10 % â 10 % â 20 % ê 20 % ê...
  • Page 62 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 2. Enter the following values for the fan powers in the respective ventilation profile via the easyControls software or the control element KWL-BE Touch: Away: 30 % / At home: 50 % / Boost: 80 % (cf. Fig. 55). 3.
  • Page 63 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D Determine fan powers: 1. Enter the flow rates from the design calculation for the three ventilation profiles “At home”, “Away” and “Boost” in the unit characteristic curve for supply and extract air (cf. Fig. 58). ⓘ...
  • Page 64: Perform Flow Rate Measurement For Adjusting The System (Fine Adjustment)

    Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 5. Enter the fan powers for supply and extract air according to the determined values for nominal ventilation under “Fan setting” (cf. Fig. 60). Fig. 60 6.3.3 Perform flow rate measurement for adjusting the system (fine adjustment) •...
  • Page 65 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D CHAPTER 7 Operating options 7.1.1 Local web server OPERATION The unit can be configured via the local web server using a web browser, via a mobile end device (e.g. notebook, PC, tablet, smartphone).
  • Page 66 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D AT HOME Ventilation profile in the presence of persons. The following parameters can be adjusted: • Fan power • Supply air The target supply air temperature is adjusted here. ⓘ...
  • Page 67 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 7.2.1.7 Weekly programme Fig. 68 • Activate/deactivate weekly programme • Create/edit weekly programme The ventilation profile changes in the following order by clicking on a field (cf. Fig. 68): Ventilation profile “At home”...
  • Page 68 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D 7.2.4 Settings 7.2.4.1 Language Select the desired language for the user interface. 7.2.4.2 Release code Change release code. ⓘ The release code is pre-set to 0000 as standard. 7.2.4.3 Cloud service Connect unit to the easyControls cloud service or disconnect cloud service.
  • Page 69 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D • Emergency off/Normal mode (0 V / 24 V) • Intensive ventilation Off/On (0 V / 24 V) • Normal mode / Bypass (0 V / 24 V) • Weekly programme Off / On (0 V / 24 V) •...
  • Page 70 The unit is equipped with filters ISO Coarse 75 % on the intake air and extract air sides as standard. The filters are available as accessories: Replacement air filter Course filter Coarse 75 % (2 pcs) ELF-KWL 220 D/4/4 Ref. no. 09638 Replacement air filter Fine/pollen filter ePM1 50% (1 pc) ELF-KWL 220 D/7 Ref.
  • Page 71 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D Activated carbon filter (instead of F7 Filter) (1 pc) ELF-KWL 220 AK Ref. no. 03050 Activated carbon filter (instead of F7 Filter) (1 pc) ELF-KWL 340 AK Ref. no. 03051 The filters can be ordered at www.Ersatzluftfilter.de Heat exchanger maintenance and cleaning 8.3.1 Heat exchanger maintenance...
  • Page 72 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D Metal tray maintenance The metal trays should be checked for functionality and cleaned, if necessary, as required but at least every 6 months. In order to prevent the intake of condensate through the fans, metal trays are mounted in the unit below the left and right motor unit.
  • Page 73 Installation and Operating Instructions Central ventilation unit – KWL 220/340 D...
  • Page 74 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D SOMMAIRE NOTICE DE MONTAGE ET D‘UTILISATION CHAPITRE 1 SÉCURITÉ .................................. PAGE 3 Informations générales ................................Page 3 Consignes de sécurité ................................Page 3 Consignes de sécurité ................................Page 3 Domaines d‘utilisation ................................
  • Page 75: Notice De Montage Et D'utilisation

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D FRANÇAIS CHAPITRE 7 COMMANDE ................................PAGE 28 Possibilités de commande ..............................Page 28 7.1.1 Serveur web local ................................Page 28 7.1.2 Service Cloud easyControls .............................. Page 28 7.1.3 Commande ..................................
  • Page 76: Informations Générales

    Filet à cheveux Le filet à cheveux empêche les longs cheveux de se coincer dans les pièces mobiles. Pour le fonctionnement, le raccordement et l’utilisation, contacter Helios en cas de doutes. Des informations supplémentaires sont consultables dans les normes et textes de loi.
  • Page 77: Domaines D'utilisation

    à des contraintes climatiques, techniques ou électroniques. Une utilisation en unité mobile (véhicules, avions, bateaux, etc.) n’est pas prévue. L‘utilisation dans ces conditions n‘est possible qu‘avec l‘accord d‘Helios, la version standard n‘étant pas adaptée à une telle utilisation.
  • Page 78: Transport

    Pour les conduits principaux (air extérieur, air rejeté, air soufflé et air extrait), le diamètre du conduit doit correspondre à un DN 125 mm (pour la KWL 220 D) et DN 160 mm (pour la KWL 340 D). Pour les conduits secondaires, le diamètre peut être réduit en conséquence en fonction du débit d‘air.
  • Page 79: Normes - Règlementations

    Si toutes les consignes indiquées dans cette notice ne sont pas correctement respectées, la garantie s’annule. Idem pour les garanties constructeur Helios. L’utilisation d’accessoires, non fournis, non conseillés ou non proposés par Helios, est interdite. Tous changements ou transformations effectués sur l’appareil sont interdits, altèrent sa conformité...
  • Page 80: Vue D'ensemble De L'appareil

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D CHAPITRE 3 Vue d‘ensemble de l‘appareil INFORMATIONS Fig. 1  SUR LE PRODUITS               ...
  • Page 81: Données Techniques

    T3 Sonde de température air extérieur Raccord à joint court Ø125/160     T4 Sonde de température air soufflé RVBD 125 K (accessoire KWL 220 D) T6 Sonde de température de gaine / KWL-LTK (accessoire) RVBD 160 K (accessoire KWL 340 D) Données techniques Données techniques...
  • Page 82: Dimensions

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D Dimensions Fig. 3 KWL 220 D R 170 193 1141 ø125 Muffe ø12 Kugel- Siphon à boule siphon air soufflé Zuluft air extérieur Außenluft air rejeté Fortluft...
  • Page 83: Données Acoustiques

    Punkte 9-12 Punkte 9-12 Max Kennlinie Max Kennlinie Volumenstrom m³/h Volumenstrom m³/h Débit volumique Débit volumique Volumenstrom m³/h umenstrom m³/h Puissance acoustique rayonnée par le caisson KWL 220 D Niveau de Débit vo- Pres- Niveau Puissance du pression Point lumique sion...
  • Page 84 Punkte 9-12 Punkte 9-1 Max Kennlinie Max Kenn Volumenstrom m³/h Volumenstrom m³/h Débit volumique Débit volumique umenstrom m³/h Volumenstrom m³/h Puissance acoustique air soufflé KWL 220 D Débit volu- Pres- Niveau Puissance du Point mique sion global ventilateur [Hz]...
  • Page 85: Puissance Acoustique Air Extrait

    Punkte 9-12 Punkte 9 Max Kennlinie Max Ken Volumenstrom m³/h Volumenstrom m³/h Débit volumique Débit volumique Volumenstrom m³/h umenstrom m³/h Puissance acoustique air extrait KWL 220 D Débit volu- Pres- Niveau Puissance du Point mique sion global ventilateur [Hz]...
  • Page 86 Punkte 9-12 Punkte 9- Max Kennlinie Max Kenn Volumenstrom m³/h Volumenstrom m³/h Débit volumique Débit volumique lumenstrom m³/h Volumenstrom m³/h Puissance acoustique air rejeté KWL 220 D Débit volu- Pres- Niveau Puissance du Point mique sion global ventilateur [Hz]...
  • Page 87: Puissance Acoustique Air Extérieur

    Punkte 9-12 Punkte 9-12 Max Kennlinie Max Kennlinie Volumenstrom m³/h Volumenstrom m³/h Débit volumique Débit volumique menstrom m³/h Volumenstrom m³/h Puissance acoustique air extérieur KWL 220 D Débit volu- Pres- Niveau Puissance du Point mique sion global ventilateur [Hz]...
  • Page 88: Instructions D'installation

    à bornes doivent être facilement accessibles. Les distances minimales suivantes par rapport au mur et au plafond doivent être respectées (voir Fig. 22). Fig. 22 KWL 220 D KWL 340 D Dimensions en mm 1.
  • Page 89: Montage Du Siphon À Boule

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D Les bacs empêchent l‘accumulation de condensat dans cette zone et il est impératif de vérifier qu‘ils sont correctement positionnés à l‘horizontal (voir Fig. 23 et Fig. 24). Fig.
  • Page 90 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D 3. Insérer la pièce de verrouillage et la pousser vers le haut (voir Fig. 29). 4. Insérer ensuite un tube d’évacuation des condensats de type DN 12 mm (non fourni) sur le tuyau de raccordement du siphon et visser manuellement (voir Fig.
  • Page 91: Variante 2 : Montage Mural

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D 4.3.2 Variante 2 : Montage mural Risque de blessure dû à la chute de la porte de l‘appareil AVERTISSEMENT La porte de l‘appareil peut tomber lorsqu‘on l‘enlève et causer de graves blessures. >...
  • Page 92: Raccordement Des Conduits De Ventilation

    Raccordement des conduits de ventilation L‘appareil est équipé de quatre manchons (Ø 125 mm (KWL 220 D) ou Ø 160 mm (KWL 340 D)) pour le raccordement au conduits. Les conduits de ventilation doivent être solidement et hermétiquement raccordés aux manchons. À cette fin, les raccords à...
  • Page 93: Schéma De Raccordement

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D 5.1.1 Schéma de raccordement Fig. 44 Longueur du câble Modbus : 100 m maximum Il faut utiliser des paires de f ils torsadés. KWL-VOC eC Surveillance à Sensor* distance du Numéro de poste: 20247...
  • Page 94: Schéma De Câblage

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D 5.1.2 Schéma de câblage Fig. 45 MB_A MB_A MB_B MB_B +24V +24V RS_A RS_A RS_B RS_B voir SS-1433 +24V RS_A +24V RS_A RS_B RS_B +11V1 +24V AN/I D/I1 Distribution électrique +24V...
  • Page 95: Première Mise En Service

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D CHAPITRE 6 Première mise en service Pour la première mise en service, l‘appareil doit être correctement raccordé au réseau électrique ou branché au secteur. MISE EN SERVICE L‘assistant de mise en service peut ensuite être mis en place via le serveur web local ou, en option, via la commande KWL-BE Touch (accessoire).
  • Page 96: Paramétrages

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D Fig. 48 4. Configurer l‘appareil et cliquer sur „Suivant“. > Le récapitulatif des paramètres s‘ouvre. 5. Vérifier les paramètres et les ajuster si nécessaire. 6. Cliquer sur „Retour“ pour ajuster les paramètres. 7.
  • Page 97 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D Fig. 49 Fig. 50 Courbe caractéristique KWL 220 D Courbe caractéristique KWL 220 D Air soufflé Air extrait 10 % â 10 % â 20 % ê...
  • Page 98 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D 3. Sélectionner les différents profils de ventilation les uns après les autres (en déplacement, à la maison, ventilation intensive) et mesurer la différence de pression statique entre l‘air rejeté et extrait puis entre l‘air soufflé et extérieur. 4.
  • Page 99 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D Déterminer les performances du ventilateur : 1. Saisir les débits volumiques issus du l‘étude pour les trois profils de ventilation „à la maison“, „en déplacement“ et „Ventilation intensive“ dans la courbe caractéristique de l‘appareil pour l‘air soufflé et extrait (voir Fig. 57). ⓘ...
  • Page 100: Réglage Par Mesure Du Débit Volumique (Réglage Fin)

    Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D valeurs déterminées pour la ventilation nominale (voir w). Fig. 59 6.3.3 Réglage par mesure du débit volumique (réglage fin) • Mesurer les débits sur toutes les bouches de soufflage et d‘extraction d‘air. •...
  • Page 101 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D CHAPITRE 7 Possibilités de commande 7.1.1 Serveur web local COMMANDE L‘appareil peut être configuré via le serveur web local à l‘aide d‘un navigateur web, via un appareil mobile (par exemple un ordinateur portable, un PC, une tablette, un smartphone).
  • Page 102 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D À LA MAISON Profil de ventilation en présence de personnes. Les paramètres suivants peuvent être définis : • Puissance du ventilateur • Air soufflé Vous régler ici la température de consigne pour l‘air soufflé. ⓘ...
  • Page 103 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D 7.2.1.7 Programme hebdomadaire Fig. 67 • Activer/désactiver le programme hebdomadaire • Créer/modifier le programme hebdomadaire En cliquant sur un champ, le profil de ventilation change dans l‘ordre suivant (voir Fig. 67) Profil de ventilation „A la maison“...
  • Page 104 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D 7.2.4 Réglages 7.2.4.1 Langue Sélectionner la langue souhaitée pour l‘interface utilisateur. 7.2.4.2 Code d‘accès Changer le code d‘accès. ⓘ Le code d‘accès 0000 est préréglé par défaut. 7.2.4.3 Service Cloud Connecter l‘appareil au service Cloud easyControls ou déconnecter le service Cloud.
  • Page 105 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D • Arrêt d‘urgence / fonctionnement normal (0 V / 24 V) • Ventilation intensive arrêt/marche (0 V / 24 V) • Fonctionnement normal / Bypass (0 V / 24 V) •...
  • Page 106 L‘appareil est équipé de série de filtres ISO Coarse 75% côté air extérieur et côté air extrait. Les filtres sont disponibles en tant qu‘accessoires : Filtre de rechange grossier Coarse 75 % (2 pcs.) ELF-KWL 220 D/4/4 N° Réf. 09638 Filtre de rechange fin/à pollen fin / à pollen ePM1 50% (1 pc.) ELF-KWL 220 D/7 N°...
  • Page 107 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D Entretien et nettoyage de l‘échangeur à contre-courant 8.3.1 Entretien de l‘échangeur à contre-courant L‘échangeur à contre-courant doit être inspecté selon les besoins ou au moins une fois par an pour détecter les salissu- res et l‘encrassement (inspection visuelle) et être nettoyé...
  • Page 108 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D Entretien des bacs métalliques Les bacs métalliques doivent être vérifiés pour leur fonctionnement et nettoyés si nécessaire au moins tous les 6 mois, en fonction des besoins. Pour éviter que le condensat ne soit aspiré...
  • Page 109 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D...
  • Page 110 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D...
  • Page 111 Notice de montage et d‘utilisation Unité de ventilation centrale – KWL 220/340 D...
  • Page 112 CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd. · 5 Crown Gate · Wyncolls Road · Severalls Industrial Park · Colchester · HELIOS Ventilatoren · Postfach 854 · Siemensstraße 15 · 6023 Innsbruck...