Iq8Hc-72-M-Us Microinverter Specifications - enphase IQ8X Installation And Operation Manual

Microinverters
Table of Contents

Advertisement

IQ8HC-72-M-US Microinverter specifications

Topic
Commonly used modules for pairing
Module compatibility
MPPT voltage range
Operating Range
Minimum/Maximum start voltage
Maximum Input DC Voltage
Max. continuous operating DC current
Max. input DC short-circuit current
Max. module I
sc
Overvoltage class DC port
DC port backfeed under single fault
PV array configuration
Peak output power
240 VAC
208 VAC
Maximum continuous AC output power
240 VAC
208 VAC
Nominal grid voltage (L-L)
240 VAC
208 VAC
Minimum and Maximum grid voltage
240 VAC
208 VAC
Max continuous output current
240 VAC
208 VAC
Nominal frequency
Extended frequency range
AC short circuit fault current over 3 cycles
Maximum microinverters per 20 A (max) AC
branch circuit
3
240 VAC
208 VAC
Total harmonic distortion
Overvoltage class AC port
AC port backfeed current
Power factor setting
Grid-tied power factor (adjustable)
34
IQ8MC, IQ8AC, IQ8HC, and IQ8X Microinverters Installation and Operation Manual
Enphase IQ8HC-72-M-US Microinverter parameters
Unit
DC parameters
1
W
V
V
V
V
A
A
A
A
AC parameters
VA
VA
V
2
V
A
Hz
Hz
A
rms
%
mA
© 2023 Enphase Energy Inc. All rights reserved.
Minimum
295–540
To meet compatibility, PV modules must be within the
following maximum input DC voltage and maximum module I
Module compatibility can be checked at
https://enphase.com/installers/microinverters/calculator
29.5
18
22
Ungrounded array; No additional DC side protection
required; AC side protection requires max 20 A per branch
circuit
split-phase (L-L), 180°
single-phase (L-L), 120°
211
183
47
0.85 leading ... 0.85 lagging
Typical
Maximum
45
58
58
60
14
25
20
II
0
384
366
380
360
264
229
1.58
1.73
60
68
2.70
10
9
<5
III
18
1.0
November 2023