enphase IQ8X Installation And Operation Manual page 22

Microinverters
Table of Contents

Advertisement

IQ8MC, IQ8AC, IQ8HC, and IQ8X Microinverters Installation and Operation Manual
Enphase Energy System PV solar grid-agnostic
In the PV Solar Grid Agnostic configuration in Enphase Energy System, IQ System Controller is installed on the line side
of the main load panels. This allows a properly sized Enphase Energy System to provide power to all loads in the main
load panel in the event of a grid outage and PV solar presence. In this configuration, the IQ System Controller can be
configured with a main breaker to act as the service disconnecting means. The PV system shall be interconnected to the
IQ System Controller on a dedicated breaker. This configuration typically supports larger PV system sizes and may allow
for avoiding expensive utility service and/or main service panel upgrades.
System commissioning for grid-agnostic configuration should be done with grid power present. During IQ8 PV
installation, ensure all relays are open from the main panel and IQ System Controller. When commissioned, IQ System
Controller gets powered on from the grid side of the microgrid interconnect device (MID); it closes the MID relay and PV
relay. IQ8 PV shall start producing power in grid-tied mode with IQ Gateway power on. Follow the Enphase Energy
System commissioning process using Enphase Installer App for system commissioning.
Enphase Energy System PV solar + storage – whole home backup
configuration
22
© 2023 Enphase Energy Inc. All rights reserved.
November 2023
USM-00008-2.0