Page 1
HPSBOC 7012D v.1.0 HPSBOC 13,8V/6A/40Ah/OC Buffer switch mode power supply unit with technical outputs. Edition: 4 from 01.04.2015 Supercedes edition: 3 from 05.06.2014...
GREEN POWER plus www.pulsar.pl HPSBOC7012D Features: EPS technical output indicating AC power loss DC 13,8V/6A uninterruptible power supply – OC and relay type fitting battery: 40Ah/12V PSU technical output indicating PSU failure wide range of mains supply: 176÷264V –...
GREEN POWER plus www.pulsar.pl HPSBOC7012D 5. Buffer power supply unit HPSBOC 13,8V/2x12V/6x1A/40Ah - HPSBOC7012D + 2xRN500 (13,8V/12V)+2xLB4 6x1A (AWZ575 or AWZ576) + 40Ah 6. Buffer power supply unit HPSBOC 13,8V/2x12V/12x0,5A/40Ah. - HPSBOC7012D + 2xRN500 (13,8V/12V)+2xLB8 12x0,5A (AWZ578 or AWZ580) + 40Ah 7.
GREEN POWER plus www.pulsar.pl HPSBOC7012D Fig. 2. The view of the PSU. Description of PSU components and connectors (tab.2, fig.3). Element no. Description [Fig. 3] PSU module TAMPER, contact, sabotage protection (NC) Tab.2. Output terminals of the PSU. Fig.3. The view of the PSU.
GREEN POWER plus www.pulsar.pl HPSBOC7012D Operation safety (tab.5) Protection class PN-EN 60950-1:2007 I (first) Protection grade PN-EN 60529: 2002 (U) IP20 Electrical strength of insulation: - between input and output circuits of the PSU (I/P-O/P) 3000 V/AC min. - between input circuit and PE protection circuit (I/P-FG) 1500 V/AC min.
GREEN POWER plus www.pulsar.pl HPSBOC7012D 2.2 Installation procedure. 1. Before installation, cut off the voltage in the 230V power-supply circuit. 2. Mount the PSU in a selected location and connect the wires. 3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the earth symbol PE (PSU module connector).
GREEN POWER plus www.pulsar.pl HPSBOC7012D 3.2 Technical outputs The PSU has indication outputs: EPS - absence of AC supply output: - OC type output that indicates AC power loss. Under normal status, with 230V AC supply, the output is connected to ground (L level –...
Page 9
GREEN POWER plus www.pulsar.pl HPSBOC7012D 4.3 Maintenance. Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network. The PSU does not require performing any specific maintenance measures, however, in case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse...
Page 10
GENERAL WARRANTY CONDITIONS 1. Pulsar (the manufacturer) grants a two-year warranty for the equipment,, counted from the device’s production date. 2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (the selection is at the manufacturer’s discretion) if the malfunction is due to the manufacturer, includes manufacturing or material defects,...