Samson TROVIS 5724-8 Mounting And Operating Instructions page 80

Without/with fail-safe action electric actuators with process controller for heating and cooling applications
Table of Contents

Advertisement

Annex A
CO/PA
Function/
designation
PID controller
C1.KP/
Proportional-action coeffi-
C2.KP
cient
C1.TN/
Reset time
C2.TN
C1.TV/
Derivative-action time
C2.TV
C1.Y0/
Operating point
C2.Y0
Manipulated variable
C1.4/C2.4
Function
C1.YP/C2.
Fixed actuator positioning
YP
value
M ...
Actuator
Actuator parameters
MY.EA
End position guiding (stem
extends)
MY.EE
End position guiding (stem
retracts)
MY.TE
Idle time during end posi-
tion guiding
MY.TZ
Dead band (switching
range)
Signal failure
A7.1
Function
A7.YP.ERR
Fixed actuator positioning
value
16-8
Setting/
adjustment range
0.1 to 999.9
0 to 999 s
0 to 999 s
0.0 to 100.0 %
0:
Controller positioning value
1:
Fixed actuator positioning value with DI1
2:
Fixed actuator positioning value with DI2
3:
Fixed actuator positioning value with DI3
4:
Fixed actuator positioning value with DI4
5:
Fixed actuator positioning value with LIM1
6:
Fixed actuator positioning value with LIM2
0.0 to 100.0 %
0.0 to 49.9 %
50.0 to 100.0 %
0 to 99 s
0.5 to 5.0 %
0:
Last travel value
1:
Fixed positioning value
0.0 to 100.0 %
EB 5724-8 EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Trovis 5725-8