Omron C200H-RM201 System Manual page 97

Rack pcs
Hide thumbs Also See for C200H-RM201:
Table of Contents

Advertisement

Error Codes and Monitoring
5903
88
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
To check for other errors, monitor 5900 and force-set the system. This
causes the next error word to be displayed.
To read the next error, reset the Error Check bit, then set it again. If the left-
most Master has an error, the following is displayed. Errors in the Slaves
cannot be read if there is an error in the Master.
This is an example program to stop PC operation if an error occurs in the
Remote Terminal allocated word 31. Operation can be restarted by first re-
moving the cause of the error, then setting and resetting the Error Check bit
until the contents of word 59 goes to 0000, and finally clearing the error via
the Programming Console.
6306
Incremented one by the Error Check flag.
Indicates Remote Terminal word 31.
Master number
Remote I/O Error flag turns
MOV(21)
ON when there is an error.
59
The first step is thus to move
DM 000
IR 59 to DM 000.
The next error is read and
its word number displayed.
5900
If there is not another error,
all 0s will be displayed.
ANDW(34)
Bits 0 to 3 are masked.
#FFF0
DM 000
DM 000
Data from DM 000 is
CMP(20)
compared with #3100.
DM 000
#3100
If data matches, there is an
FALS(07)
error in the Unit allocated
01
word 31 and the CPU Unit
stops.
END(01)