Wiring
C200H-RT202
Power Supply Wiring
Precautions
68
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Fuse
Terminals
Use thick cables (1.25 mm
M3.5 self-rising terminals screws are used for the terminal block. When wir-
ing to the terminal block, use crimp terminals for M3.5 screws. Do not con-
nect stranded wires directly to the terminal block.
Tighten the screws on the terminal block to a torque of 0.8 N m.
+
24 VDC
Use a 24-VDC power supply.
NC
NC
Connect to independent ground to reduce
LG
noise interference and prevent shock.
*
GR
Connect to independent ground to
prevent shock.
NC
NC
ON while the system is operating.
RUN output
* The LG and GR terminals are
connected internally.
M3.5
7.3
2
min.) to prevent against voltage drops.