Wiring
C200H Slave Connectors
C200H-RT201
Fuse
AC Power Supply Wiring
Precautions
!
Caution
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
C200H Slaves use a 2-piece connector. When attaching this connector, press
down firmly until you hear it lock into place, and then confirm that the lock
lever is in place. The connectors are wired as shown below.
AC input
Voltage switch
Shorted: 100V
Open:
LG
GR
+
+
24 VDC output
RUN output
Terminals
Use thick cables (1.25 mm
M3.5 self-rising terminals screws are used for the terminal block. When wir-
ing to the terminal block, use round crimp terminals with the M3.5 screws. Do
not connect stranded wires directly to the terminal block.
Tighten the screws on the terminal block of the AC Power Supply Unit to a torque
of 0.8 N m. Loose screws may result in short-circuiting, malfunction, or burning.
Power supplied at either 100 to 120 VDC
or 200 to 240 VDC
Use enclosed device to short for 100-V
power supply. When using 200-V power
supply, verify that circuit is open.
200V
Connect to independent ground to reduce
noise interference and prevent shock.
*
Connect to independent ground to pre-
vent shock.
Use to power DC Input Units. Use a sepa-
rate power supply if exceeding 3.0 A. If
0.3 A
3.0 A is exceeded, PC may detect error
and stop operation.
ON in RUN mode. Use for accessing sig-
nals from PC in RUN mode.
* The LG and GR terminals are
connected internally.
M3.5
3 max.
7.3
2
min.) to prevent against voltage drops.
Section 5-5
67