6.7.4 Menu description "A Quick Setup"

Function
A1 Language
A2 Contrast
A3 Login
A4 Tag
A5 Long Tag
A6 Message View
A7 Fluid
A8 Medium
A9 Units
A10 Meter Type
A11 Application Assistant
A12 Cluster Checks
Table 6-20: Menu description "A Quick Setup"
08/2022 - A5E36751269-AG EN
Setting / Description
For availability of display languages refer to Menu languages on page 62.
Adjust contrast of local display (-10...+10; Standard = 0)
Enter password: 0000 (to change password refer to menu C6.2.2)
Entry and display of measuring point identifier (8 digits).
Entry and display of long measuring point identifier (1...32 digits).
Entry will be displayed in the header bar on the LC display (depending on letter size,
min. 11 digits can be displayed).
NAMUR messages (F, S, M, C, I)
For further information refer to Status messages and diagnostic information on page
92.
Select: Liquid / Steam / Gas / Wet Gas / Gas Mixture
Depending on selected fluid, appropriate medium can be selected in A8
If fluid is "Gas" or "Wet Gas" (for details refer to Gas options for gas measurement on
page 63)
The following selection is available for fluid = "Steam":
Saturated Steam / Superheated Steam / Custom
The following selection is available for fluid = "Liquid":
Water / Custom
The following selection is available for fluid = "Wet Gas":
Here, a gas can be selected as a wet gas from all of the above mentioned gases.
For further information refer to menu C6.5.
Standard:
For liquids, gases and steam; integrated temperature compensation for saturated
steam.
Heat:
For liquids, gases and steam; integrated temperature compensation for saturated
steam, gross/net heat measurement for saturated steam and water.
Heat & Dens. by Pres.:
Integrated density compensation for saturated steam, superheated steam and gas,
gross/net heat measurement for saturated steam, superheated steam and water.
Heat & Dens. & FAD:
Integrated density compensation for saturated steam, superheated steam and gas,
gross/net heat measurement for saturated steam, superheated steam and water, FAD
functionality.
For details refer to next tables.
For further information refer to A12 plausibility checks on page 98.