SITRANS FX330
A11.1 Application Assistant - Liquids
Function
.1
.2 Units
.2.1 Volume Flow
.2.2 Mass Flow
.2.3 Volume
.2.4 Mass
.2.5 Temperature
.2.6 Pressure
.2.7 Density
.3 Process
.3.1 Fluid
.3.2 Medium
.3.3 Time Constant
.3.4 Low Flow Cutoff
.4 Operating Values
.4.1 Oper. Temperature
.4.2 Oper. Pressure
.4.3 Oper. Density
.5 Current Output
.5.1 Current Out. Meas.
.5.2 0% Range
.5.3 100% Range
.5.4 Error Function
.5.5 Low Error Current
.5.6 High Error Current
.6 Binary Output
.6.1 Function
.6.2 Invert Signal
.7 Pulse Output
.8 Frequency Output
.9 Status Output
.10 Limit Switch
.11 Flow Totalizer
.12 Energy Totalizer
.13 1. Meas. Page
.14 2. Meas. Page
Table 6-22: A11.1 Application Assistant - Liquids
08/2022 - A5E36751269-AG EN
Setting / Description
Select unit (default: according to order specification or m
Select unit (default: according to order specification or kg/h).
Select unit (default: according to order specification or m
Select unit (default: according to order specification or kg).
Select unit (default: according to order specification or °C).
Select unit (default: according to order specification or bar).
Select unit (default: according to order specification or kg/m
Process configuration.
Select "Liquid".
Select "Water" or "Custom".
0...100 s
Enter low flow cutoff point in current volume flow unit.
Current process conditions in case they are not measured nor calculated.
Input in selected unit.
Input in selected unit.
Input in selected unit.
Current output configuration.
Select measurement variable for current output.
The set value represents 4 mA at the current output. Usually 0% flow = 4 mA, but it is
also possible to define a higher flow value for 4 mA.
The set value represents 20 mA at the current output. Usually 100% flow = 20 mA, but it
is also possible to define a lower flow value for 20 mA.
Low / Off / High / Hold
3.5...3.6 mA, available if "Error Function = Low"
21...21.5 mA, available if "Error Function = High"
Optionally configure the binary output.
Select the binary output function:
Limit Switch / Status / Frequency / Pulse / Off
On, Off
This menu is available if "Binary Output Function = Pulse".
This menu is available if "Binary Output Function = Frequency".
This menu is available if "Binary Output Function = Status".
This menu is available if "Binary Output Function = Limit Switch".
Optionally configure the flow totalizer.
This menu is available if a non-standard meter type has been configured (refer to "C6.3
Extras").
One Value / Two Values / Three Values / One Value & Bargraph / Two values &
Bargraph
One Value / Two Values / Three Values / One Value & Bargraph / Two values &
Bargraph
www.siemens.com/flow
OPERATION
3
/h).
3
).
3
).
6
75