Siemens SITRANS FX330 Operating Instructions Manual page 110

Vortex flowmeters
Table of Contents

Advertisement

TECHNICAL DATA
8
Foundation Fieldbus
Description
Function blocks
Output data
Approvals and certificates
Declaration of conformity
Standard version
Functional safety according to
IEC 61508
Hazardous areas
ATEX / UKEx
IECEx
QPS (USA & Canada)
Other standards and approvals
QPS (USA & Canada)
NAMUR
Further approvals on request.
110
Galvanically isolated according to IEC 61158-2
Current consumption: 16 mA
Permissible bus voltage: 9...32 V; intrinsically safe: 9...24 V
Bus interface with integrated reverse polarity protection
Link Master function (LM) supported
Tested with Interoperable Test Kit (ITK) version 6.1
5 x analog input (AI), 2 x Integrator (IT), 1 x PID, 1 x analog output (AO)
Volume flow, mass flow, norm. volume flow, corrected volume flow, temperature 1,
temperature 2, pressure, density, velocity, gross power, net power, FAD, vortex
frequency, Reynolds number, specific heat capacity, specific enthalpy, sensor
electronics temperature, converter electronics temperature, diagnostic data
This device fulfils the statutory requirements of the relevant directives and regulations.
The manufacturer certifies successful testing of the product by applying the conformity
mark on the device.
For further information on directives, regulations, standards and certifications, please
refer to the declaration of conformity.
Non-Ex
Depends on I/O variant and flow sensor. For detailed information refer to the "Safety
manual".
ATEX II2 G - Ex ia IIC T6...T2 Gb
ATEX II2 G - Ex d ia IIC T6...T2 Gb (not for signal converter in stainless steel housing)
ATEX II3 G - Ex nA IIC T6...T2 Gc (not for signal converter in stainless steel housing)
ATEX II2 D - Ex tb IIIC T70 Db (not for signal converter in stainless steel housing)
IECEx - Ex ia IIC T6...T2 Gb
IECEx - Ex d ia IIC T6...T2 Gb (not for signal converter in stainless steel housing)
IECEx - Ex nA IIC T6...T2 Gc (not for signal converter in stainless steel housing)
IECEx - Ex tb IIIC T70°C Db (not for signal converter in stainless steel housing)
QPS IS Class I Div 1
QPS XP Class I Div 1 (not for signal converter in stainless steel housing)
QPS NI Class I Div 2 (not for signal converter in stainless steel housing)
QPS DIP Class II, III Div 1 (not for signal converter in stainless steel housing)
QPS Ordinary Locations
NE 06, NE 21, NE 23, NE 32, NE 43, NE 53, NE 107
www.siemens.com/flow