Parameters Settings - Tekno Point ATHENA C200 User And Installation Manual

All in one centrifugal heat pump
Table of Contents

Advertisement

Available languages

Available languages

E-Heater manual startup
To start manual electric heating manually, it is necessary, in the ON state, to press
simultaneously for 5 seconds to enter/exit forced electric heating.
The option will work only if the outdoor temperature threshold, set in parameter b13, is met.
Check background failure of protection 2
In On status, press
if there is no failure. Press
Restore factory settings
In ON status, press
after 10 seconds to save the setting, and turn on again after 10 seconds.

Parameters settings

Parameter changes may only be made by trained personnel authorised by the manufacturer.
1.In main menu, press
to set parameters. Press
2. In parameter setting menu, if there is no operation for 30 seconds, will automatically exit parameter setting
and back to main menu. Or press
Item Description
Water difference to start compressor in hea-
b01
ting mode
Water difference to start compressor in coo-
b02
ling mode
b03
Max. set temperature in heating mode
b04
Min. set temperature in heating mode
b05
Max. set temperature in cooling mode
b06
Min. set temperature in cooling mode
b07
Water temperature compensation
b08
Circulation running mode
b09
Circulation pump interval time
Inlet and outlet water temperature
b10
difference protection value
b11
Working mode
b12
Power lost memory function
66
button for 10 seconds to check background failure of protection 2. It displays "----"
button to back to main menu.
and
button simultaneously for 3 seconds till there is sound "Di". Turn off
button for 3 seconds to enter parameter setting menu, press
button to save setting..
button to back to main menu.
Default
Unit
Range
value
3
°C
3
°C
60
°C
20~60
15
°C
10~20
32
°C
20~60
8
°C
0
°C
2
5
min
13
°C
3
1
and
buttons
or
Remark
0~15
0~15
7~20
-9~9
0: run 2 mins every
b09 mins
0~2
1: run as compressor
run
2: always run
0~99
5~40
0: heating
1: heating+DHW
2: heating+cooling
3: heating+cooling+-
0~1
DHW
After setting, it needs
to be powered off to
take effect.
0: off
0~1
1: on