Fouling factors
The performance data given refer to conditions with clean evaporator plates (fouling factor=1). For
different fouling factors, multiply the figures in the performance tables by the coefficient given in the
following table.
Fouling factors
(m
°C/W)
2
4.4 x 10
-5
0.86 x 10
-4
1.72 x 10
-4
Anti-freezing protection
1. In Off or Standby status, enter anti-freezing protection if satisfy the following conditions:
a) When environment temperature ≤ 4 °C, and inlet water temperature ≤ 6 °C for 3 minutes,enter first
stage anti-freezing; when detect the circulating pump power off continuously for over 30 minutes
continuously, force to run the circulation pump for 3 minutes, then stop, run periodically. Exit first stage
anti-freezing till inlet water temperature ≥ 8 °C, or environment temperature ≥ 6 °C for 3 minutes.
b) When environment temperature ≤ 4 °C, and inlet water temperature ≤ 4 °C for 3 minutes, enter second
stage anti-freezing; and force to run heating, exit the second stage anti-freezing till inlet water tempe-
rature ≥ 15 °C or environment temperature ≥ 6 °C for 3 minutes.
2. If environment temperature sensor faults, the anti-freezing is decided by inlet water temperature only; if inlet
water temperature sensor faults, the anti-freezing is decided by environment temperature only, and enter first
stage anti-freezing only.
3. If there is fault causes compressor can't start, enter first stage anti-freezing only, can't enter the second stage
anti-freezing.
4. If both environment temperature sensor and inlet water temperature sensor fault, when outdoor coil tempera-
ture ≤ 0 °C, enter first stage anti-freezing only, exit anti-freezing when outdoor coil temperature ≥ 2 °C, after
enter standby status, enter anti-freezing, if outdoor coil temperature faults, don't exit antifreezing.
5. If environment temperature sensor, inlet water temperature sensor and outdoor coil temperature all fault, when
outlet water temperature ≤ 4 °C, enter first stage anti-freezing, controller display error code, and force to run
circulating pump till outlet water temperature ≥ 6 °C to exit anti-freezing, and detect every 5 minutes to run
circulating pump.
6. If there is fault of water flow switch, can enter first stage anti-freezing only, can't enter second stage anti-free-
zing; after enter anti-freezing, if there is fault of water flow switch, then display error code, still run circulating
pump according to anti-freezing logic.
De-Frosting Conditions
1. When -5°C≤Ta<5°C, Tc<(Ta-b22) for 3 minutes, accumulated running time of compressor>45+b20 minutes,
enter defrosting.
2. When -12°C≤Ta<-5°C, Tc<(Ta-b23) for 3 minutes, accumulated running time of compressor>45+b21 minutes,