Accessories; Fouling Factors; Anti-Freezing Protection; De-Frosting Conditions - Tekno Point ATHENA C200 User And Installation Manual

All in one centrifugal heat pump
Table of Contents

Advertisement

Available languages

Available languages

Accessories

Accessories inside the package as below table.
No
Item
1
Instruction Manual
2
Condensate drainage connector
3
Shockproof rubber pads
4
Shockproof rubber pads for DHW module
5
Wire controller

Fouling factors

The performance data given refer to conditions with clean evaporator plates (fouling factor=1). For
different fouling factors, multiply the figures in the performance tables by the coefficient given in the
following table.
Fouling factors
(m
°C/W)
2
4.4 x 10
-5
0.86 x 10
-4
1.72 x 10
-4

Anti-freezing protection

1. In Off or Standby status, enter anti-freezing protection if satisfy the following conditions:
a) When environment temperature ≤ 4 °C, and inlet water temperature ≤ 6 °C for 3 minutes,enter first
stage anti-freezing; when detect the circulating pump power off continuously for over 30 minutes
continuously, force to run the circulation pump for 3 minutes, then stop, run periodically. Exit first stage
anti-freezing till inlet water temperature ≥ 8 °C, or environment temperature ≥ 6 °C for 3 minutes.
b) When environment temperature ≤ 4 °C, and inlet water temperature ≤ 4 °C for 3 minutes, enter second
stage anti-freezing; and force to run heating, exit the second stage anti-freezing till inlet water tempe-
rature ≥ 15 °C or environment temperature ≥ 6 °C for 3 minutes.
2. If environment temperature sensor faults, the anti-freezing is decided by inlet water temperature only; if inlet
water temperature sensor faults, the anti-freezing is decided by environment temperature only, and enter first
stage anti-freezing only.
3. If there is fault causes compressor can't start, enter first stage anti-freezing only, can't enter the second stage
anti-freezing.
4. If both environment temperature sensor and inlet water temperature sensor fault, when outdoor coil tempera-
ture ≤ 0 °C, enter first stage anti-freezing only, exit anti-freezing when outdoor coil temperature ≥ 2 °C, after
enter standby status, enter anti-freezing, if outdoor coil temperature faults, don't exit antifreezing.
5. If environment temperature sensor, inlet water temperature sensor and outdoor coil temperature all fault, when
outlet water temperature ≤ 4 °C, enter first stage anti-freezing, controller display error code, and force to run
circulating pump till outlet water temperature ≥ 6 °C to exit anti-freezing, and detect every 5 minutes to run
circulating pump.
6. If there is fault of water flow switch, can enter first stage anti-freezing only, can't enter second stage anti-free-
zing; after enter anti-freezing, if there is fault of water flow switch, then display error code, still run circulating
pump according to anti-freezing logic.

De-Frosting Conditions

1. When -5°C≤Ta<5°C, Tc<(Ta-b22) for 3 minutes, accumulated running time of compressor>45+b20 minutes,
enter defrosting.
2. When -12°C≤Ta<-5°C, Tc<(Ta-b23) for 3 minutes, accumulated running time of compressor>45+b21 minutes,
58
0.96
0.93
Evaporator
Fk1
0.99
0.98
Quantity
1
2
4
6
1
0.99
0.98