Technical Data; Electrical Data - Kaco blueplanet 29.0 TL3 Operating Instructions Manual

Hide thumbs Also See for blueplanet 29.0 TL3:
Table of Contents

Advertisement

Technical Data

4
Technical Data
EN
EN
4.1

Electrical data

Input levels
Recommended power range of the generator [kW]
MPP@Pnom from [V] to [V]*
Operating range from [V] to [V]
Nominal voltage/ Starting voltage [V]
No-load voltage (U
Max. input current [A]
Max. power of the MPP tracker [W]
Number of DC connections
Number of MPP controls
max. short-circuit current (I
max. input source feedback current [A]
Polarity safeguard
Output levels
Rated power [VA]
Grid voltage [V]
Voltage range [V]
Rated current [A]
Max. continuous current [A]
Nominal frequency / frequency range [Hz]
cos phi
Number of feed-in phases
Distortion factor (THD) [%]
General electrical data
Max. efficiency [%]
European efficiency [%]
Power consumption: standby [W]
Feed-in starts at [W]
Circuit design
Grid monitoring
Table 1:
Electrical data
Page 10
) [V]
OC max
) [A]
SC max
29.0 - 40.0
360 - 900
360*... 1,050
410 / 460
1,100
85
29,900
1 (S/M version) / 6 (XL version)
1
190
0
no
29,000
138/240 (3 / N / PE);
127/220; 120/208 (3 / N / PE)
95 -200 (Ph-N) / 166-346 (Ph-Ph)
3x 69.8@240 V; 3x 76.1 @220 V; 3x 76.5 @208 V
76.5
50/60 / 42 - 68
0.30 inductive ... 0.30 capacitive
3
< 1.6
97.0
96.5
2.5
120
Transformerless
Country-specific