7.10 - Error message codes: errors, solutions and operating in case of error

Note:
Errors can be dismissed by briefl y pressing the dial (manual reset)
Display
Error
•Electronic board defect
MEMO/BUS
•Bus wire defect
•Display screen defect
•Underfl oor heating water sensor
defect
t_AIR
(temperature of water inlet from the
underfl oor heating circuit)
•Evaporator sensor defect
T_Defrost
(de-frosting temperature)
T_water
•Tank water sensor defect
clock
•Clock/timer defect
over press
•Heat pump pressure too high
low pres.
•Heat pump pressure too low
•Domestic hot water overheating
overheat
(water temperature >87°C)
cold evap
•Heat exchanger temperature too low.
err.
Risk of ice.
• The anti-legionellosis cycle is not
ANTI BAC
validated
Incorrect
reading
temperature sensor
• Incorrect reading from the defrosting
err.01
sensor
• The heat pump has run out of
refrigerant fl uid
• Expansion valve is not working
• The compressor is not working
and safety temperature is activated
• Incorrect defrosting and water
err.04
sensor readings
-
INSTALLER
Probable causes
•Voltage too high on electrical network
•Wiring error during electrical connection
(connection to electricity provider or
moisture sensor.)
•Damage during transportation
•Sensor not functioning
•Sensor unplugged from board
•Sensor cable damaged
•Sensor not functioning
•Sensor unplugged from board
•Sensor cable damaged
•Sensor not functioning
•Sensor unplugged from board
•Sensor cable damaged
•Voltage too high on electrical network
•Damage during transportation
•No water in the tank
•Water is too hot (>75°C)
•Water sensor removed from tank
•Defective water sensor
•No water fl ow
•Circulator
pump
blocked
functioning
•Circulator not properly purged
•Defective water sensor
•Water sensor removed from tank
•No water circulating (fi lter clogged,
underfl oor circulting valve is closed)
•Incorrect connection to the underfl oor
heating return fl ow inlet (inlet/outlet
reversed)
•Circuit not properly purged
•Circulator pump not functioning
•Sub-draft too high
•Set temperature too high
•Failure of the resistance
•Electrical back-up not allowed
• The air and defrosting sensors are
inverted on the electronics board
•The defrosting and water sensors
are inverted on the electronics
from
the
board
•The defrosting sensor is
connected to the air input, the
air sensor is connected to the
water input, the water sensor is
connected to the defrosting input
• The defrosting sensor is not
properly connected and she is measuring
air
• There is a leak in the refrigerant
circuit
• The expansion valve bulbs damaged or
broken due to work being carried out on
the appliance, or it being in contact
with a part that vibrates
• Defect in compressor
• The defrosting and water sensors
are inverted on the electronics
board
DOMESTIC HOT WATER HEAT PUMP 200L & 270L
Temporary operating
measures while waiting for
the problem to be resolved
•Heat pump non-functional
•Heat pump non-functional
•Electrical back-up heats water to
43°C (38°C minimum)
•Heat pump non-functional
•Electrical back-up heats water to
43°C (38°C minimum)
•Heat pump non-functional
•Programmed
heating
are no longer valid: the water is
maintained continuously at the
standard set temperature (if no
signal or control is connected to
the «external control» switch)
•Heat pump is non-functional
•Automatic reset
•Heat pump non-functional
or
not
•Electrical back-up heats the water
to 43°C (38°C minimum)
•Heat pump non-functional
•Automatic reset
Heat pump non-functional.
Electrical back-up heats water to
o
o
43
C (38
C minimum)
•Unit on
•Heat pump is non-functional
•Heat pump is non-functional
Solutions
•Replace main electronics board
or
•Replace display screen board
•Replace sensor
•Replace sensor
•Replace sensor
periods
•1-Press «clock settings» and set date
and time
•2-If the error message does not
disappear, replace the electronics
board
•Check that the tank has been properly
fi lled with water and purged of air
•Change the water sensor
•Check that the water sensor is in the
right position in the tank
•Check that the circulator pump is
working
•Check if the circulator pump is
clogged, and unclog if necessary
•Check that the sensor is in the right
position in the tank
• Clean the fi lters
•Check that water is fl owing freely
•Check
compliance
of
connection (inlet/outlet)
•Purge air at the circulator pump
•Check that the circulator pump is
working properly
•Restart a cycle
•Reduce cycle set temperature
•Clean the resistance
•Replace the resistance
•Authorize electrical back-up
• Reposition the temperature
sensors correctly on the main
electronics board
• Reposition the defrosting sensor
properly in the tube
• Find and repair the leak before
fi lling the refrigerant circuit
• Replace the expansion valve
• Replace the compressor
• Reposition the temperature
sensors properly on the main
electronics board
-
MANUAL
hydraulic
29