Hisense Hi-FLEXi S Series Technical, Installation, Maintenance page 276

Vrf air-conditioner
Table of Contents

Advertisement

3.2 Electronic Expansion Valve
Micro-Computer
2-Phase Permanent Magnetic Pulse Motor
Control 0 to 2950 Pulse by 1 Pulse (EVO)
Control 0 to 480 Pulse by 1 Pulse (EVB/MV5)
Refrigerant Flow Control
Precise Control
Specification
Items
Models to be Applied
Type
Refrigerant Used
Working Temperature Range
Mounting Direction
Flow Direction
Rated Voltage
Drive Condition
Coil Resistance
Wiring Diagram,
Drive Circuit and
Activation Mode
Pulse Signal
For Main Cycle (EVO)
PAM Series
Drive shaft in Vertical Direction
within an Angle of 90o as Maximum
100 - 200 PPS
2-2 Phase Excitation
100Ω
φ1
φ3
Phase
1
2
φ1
ON
OFF
φ2
ON
ON
φ3
OFF
ON
φ4
OFF
OFF
OPEN: 4→3→2→1→4
CLOSE: 1→2→3→4→1
Needle
Specification
R410A
-22 - 158°F( -30℃ - 70℃ )
Reversible
DC12V+1.2V
M
φ2
φ4
3
4
Phase
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OPEN: 1→2→3→4→5→6→7→8
CLOSE: 8→7→6→5→4→3→2→1
267
Pulse Motor
For Bypass Line (EVB/MV5)
UKV Series
Drive shaft in Vertical Direction
within an Angle of 45o as Maximum
80+5 PPS
1-2 Phase Excitation
46Ω+3Ω (at 20℃ )
φ2
φ4
φ1
1
2
3
4
φ1
ON
ON OFF OFF OFF OFF OFF ON
φ2
OFF OFF OFF OFF OFF ON
φ3
OFF OFF OFF ON
φ4
OFF ON
ON
ON OFF OFF OFF OFF
Main Parts
M
φ3
5
6
7
8
ON
ON
ON
ON OFF OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents