(8) Remove the terminal box cover for the compressor and disconnect the wiring to the compressor terminals. Then,
check the terminal Nos. and the mark band Nos.. Match the terminal Nos. with the mark band Nos. when rewiring the
compressor. If they are incorrectly connected, the compressor may be damaged due to reverse rotation.
NOTE:
1. When replacing the compressor, check for the ring terminal condition. If there is something wrong with any of the ring
terminals, replace it with a new one.
2. Fix the lead wire firmly with plastic ties
3. Re-tighten the compressor screws after the replacement.
Ring Terminal
(9) Release the spring for the crankcase heater to remove it.
TURN OFF all the power switches.
Mark Band
Tool
Phillips Screwdriver, Spanner
Tool
Long-nose Pliers
Spring
Crankcase Heater