Ntp Settings (Offline); Ptp Settings (Offline); Table 23: Ntp And Strata Settings - Novatech Kronos 2 Series User Manual

Table of Contents

Advertisement

5.7

NTP Settings (Offline)

This section configures the NTP (Network Time Protocol) settings. The same settings can be made in the
webpage as described in
NTP Settings
# Settings for the Network Time Protocol
# Specify stratum to report when in HOLDOVER, LOWQUALITY and BADTIME states
[NTP]
ENABLE_A = TRUE
ENABLE_B = FALSE
STRATUM_HOLDOVER = 0
STRATUM_LOWQUALITY = 1
STRATUM_BADTIME = 11
Parameter
[NTP]
ENABLE_A
ENABLE_B
STRATUM_HOLDOVER
STRATUM_LOWQUALITY
STRATUM_BADTIME
5.8

PTP Settings (Offline)

This section configures PTP for ports B, C, and D. It is recommended to configure the PTP settings with
the webpage
(PTP Settings
profile, the webpage automatically populates all parameters with appropriate values. The actual name of
the profile selected in the webpage is not stored in the configuration.
# PTP Settings
[PTP]
ENABLE_B = TRUE
LAYER_B = L2
DOMAIN_B = 254
PRIORITY1_B = 128
PRIORITY2_B = 128
PATHDELAYMECHANISM_B = P2P
ANNOUNCEINTERVAL_B = 1
ANNOUNCETIMEOUT_B = 3
SYNCINTERVAL_B = 1
(Online).
Description
Section name for NTP settings.
TRUE enables NTP for the respective port.
FALSE disables NTP for the respective port.
Stratum to be reported by the NTP service during HOLDOVER. Values
between 0 and 5 are accepted.
Default: 0
Stratum to be reported by the NTP service during LOWQUALITY. Values
between 0 and 9 are accepted.
Default: 0
Stratum to be reported by the NTP service during BADTIME. Values between
0 and 14 are accepted.
Default: 0

Table 23: NTP and strata settings

(Online)) instead of in the configuration file since after the selecting the desired
43
Kronos Series 3