Figure 17: Outputs Settings; Table 7: Outputs Settings - Novatech Kronos 2 Series User Manual

Table of Contents

Advertisement

Note: The polarity (normal, inverse) can only be configured offline as described in
The single unmodulated output cart (-1) has one output. The dual unmodulated output card (-2), the dual
modulated output card (-A), and the fiber output card (-F) have two outputs each. The quad unmodulated
output card card (-4) has four outputs.
The example in
Figure 17
Appendix A – Options List
See
number and type of outputs available in your unit.
For each output, the output type and the time setting can be configured.
Item
Description
Output type
Depending on the card, the following output types can be selected:
Default: OFF
Time
The output can be set to send either UTC time or local time.
UTC
Local

Figure 17: Outputs settings

shows a Kronos Series 3R with one -1 output card.
for information about how to interpret the part number and determine the
Card Name
Card Type
-1
Single unmodulated output
-2
Dual unmodulated outputs
-4
Quad unmodulated outputs
-F
Dual fiber outputs
-A
Dual modulated outputs

Table 7: Outputs settings

27
Kronos Series 3
Output Settings
(Offline).
Signals
OFF
PPM
PPS
IRIG-B000
IRIG-B002
IRIG-B004
IRIG-B006
OFF
IRIG-B120
IRIG-B122
IRIG-B124
IRIG-B126