Main Menu; Unit Information - SystemAir SAVE VTC 200-1 Service & Accessories Installation Manual

Hide thumbs Also See for SAVE VTC 200-1:
Table of Contents

Advertisement

8
| Configuration
Icon
Cooling recovery
Free cooling
Moisture transfer
Defrosting
Secondary air
Vacuum cleaner
Cooker hood
User Lock
Configurable
Digital Input 1
Configurable
Digital Input 2
Configurable
Digital Input 3
Pressure guard
3.5

Main menu

3.5.1

Unit Information

A basic read-only information about status of the unit, configured components and inputs/outputs.
3.5.1.1 Components
Type and settings of heat exchanger, heater, cooler, extra controller.
Text
Automatic cooling recovery is active when extract air temperature from
apartment is lower than outdoor air temperature and there is a cooling demand
(temperature setpoint is lower than outdoor air temperature).
No cooling recovery with heating demand. If the outdoor air temperature is
higher than then thee indoor air temperature and there is a heating demand,
function Free heating is activated instead.
Function decreases indoor air temperature by using only cool outdoor air during
nighttime to save energy consumption.
Function controls the rotation speed of the heat exchanger to prevent moisture
transfer to supply air due to high relative humidity in the extract air.
Function is only available for units with Rotating type heat exchanger.
Function prevents formation of the ice on the heat exchanger during cold
outdoor temperatures.
Warm air from the living space is used to defrost the heat exchanger using a
damper inside the outdoor air duct. The unit switches from outdoor air to
secondary air while the extract air fan stops and warm secondary air increases
the temperature inside the heat exchanger.
Function sets speed of supply air fan to High level and extract air fan to Low
level to increase air pressure within the apartment for better dust collection
through central vacuum cleaner.
Function can be activated via digital input — Central Vacuum Cleaner
Function.
Always active while digital input is activated.
Sets speed of both supply and extract air fans to Maximum level to increase
airflow in the cooker hood.
Function can be activated via digital input — Cooker Hood Function.
Function indicates that the system is locked with a password and cannot be
edited or settings changed in any way. System must be unlocked first to make
changes.
Configurable digital input for custom user function. Airflow levels for both fans
are freely configurable.
High–priority function.
Configurable digital input for custom user function. Airflow levels for both fans
are freely configurable.
Mid–priority function.
Configurable digital input for custom user function. Airflow levels for both fans
are freely configurable.
Low–priority function.
Configurable digital input for pressure guard connection. Airflow levels for both
fans are freely configurable.
Description
| v1