| Configuration
3.3.2

Temperature settings

Temperature can be set at SET TEMPERATURE menu accessible from the home screen by touching
TEMPERATURE icon with thermometer. Default temperature value is 18°C (range 12–30°C).
Then touch the OK button to confirm changes.
Temperature set point is for room air temperature, supply air temperature or for extract air temperature depending on
which control mode is active. Default setting is Supply air temperature control.
Control mode of the temperature can be changed in Service menu.
3.3.2.1 ECO mode
ECO mode is a power saving function that can be activated in SET TEMPERATURE menu.
ECO mode function is available only when an internal heater is installed and configured.
While ECO mode is active, a temperature setpoint at which heater is activated is lowered to avoid activation of the heat-
er during cold nighttime.
If the temperature is very low and the heater is activated during the nighttime (even with lowered temperature set-
point), then during the upcoming daytime indoor temperature will be increased using the heat exchanger so that accu-
mulated heat could be used during the next cold nighttime, the lowered setpoint for the heater remains.
ECO mode will have impact for the following user
functions/modes if selected:
• Auto
• Manual
• Away
• Holiday
• Central Vacuum Cleaner Function
• Cooker Hood Function
• Fireplace
3.3.3

Airflow settings

Airflow settings are available only in MANUAL mode. Click on fan icon on the main screen to enter SET
AIRFLOW menu.
Use up and down arrows or a slider to change the value.
ECO mode is always activated by the following modes:
• Away
• Holiday
ECO mode is always deactivated by the following user
functions/modes:
• Crowded
• Refresh
• Free cooling
| v1