VLT® HVAC Drive FC 102
Operating Guide
Enclosure
E5h
E5h
E6h
E6h

10.7.3 dU/dt Filter Specifications

Voltage rating
Motor frequency derating, 50 Hz
Motor frequency derating, 60 Hz
Motor frequency derating, 100 Hz
Minimum switching frequency
Maximum switching frequency
Overload capacity

10.7.4 Sine-wave Filter Specifications

Voltage rating
Nominal current @ 50 Hz
Motor frequency with derating
Motor frequency without derating
Minimum switching frequency
Maximum switching frequency
Overvoltage category
Overload capacity
Ambient temperature [°C (°F)]
Storage temperature [°C (°F)]
Transport temperature [°C (°F)]
Altitude during operation
Noise level
The current ratings for the E5h and E6h enclosures are achieved by filter paralleling.
1
2
See
Illustration
77.
Danfoss A/S © 2021.11
Model
N560
N630
N710
N800
(1)
(2)
Impedance [%)
212 A and 315 A for 380–480 V, 137 A and 222 A for 525–690 V
2 kHz for 380–480 V, 1.5 kHz for 525–690 V
100% current (no derating) up to 1000 m (3280 ft)
1% current derating for each 100 m (328 ft) above 1000 m
Maximum 4000 m (13123 ft) with 500 V AC
Maximum 2000 m (6561 ft) with 690 V AC
AQ262141314214en-000301 / 130R0880 | 167
Specifications
3.55
4.04
3.19
3.70
3x380–690 V
Nominal
Nominal
0.75 x nominal
No limit
Nominal switching frequency
150% for 60 s, every 10 minutes
3x380–480 V and 525–690 V AC
Up to 150 Hz
0–60 Hz
Nominal switching frequency
OVC III as defined in IEC61800-5-1
150% for 60 s every 10 minutes
-15 (5) to +60 (140)
-40 (-40) to +70 (158)
-40 (-40) to +70 (158)
(3280 ft)
< 80 dB(A)
(1)