Recommended Fuse Ratings For Ul Installation - Danfoss VLT HVAC Drive FC 102 Operating Manual

110-800 kw, d9h-d10h and e5h-e6h enclosed drives
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

VLT® HVAC Drive FC 102
Operating Guide
Model
Fuse P/N
N315
Mersen NH3GG69V425
N400
Mersen NH3GG69V500
N450
Mersen NH3GG69V500
N500
Mersen NH4GG69V630
N560
Mersen NH4GG69V800
N630
Mersen NH4GG69V800
N710
ABB OFAA4AM1000
N800
ABB OFAA4AM1000

5.9.3 Recommended Fuse Ratings for UL Installation

The fuses and MCCBs contained in the enclosed drive are suitable for both short circuit and branch circuit protection. Use only these
fuses.
UL Approval is valid for maximum input voltage of 600 V. Per UL508A, the short-circuit current rating (SCCR) is as follows:
Enclosed drives with a fusible disconnect or fusible disconnect and contactor option have 65 kA SCCR at the rated voltage.
Enclosed drives with single switchgear (mains contactor only or non-fusible disconnect only option) have a 5 kA SCCR, but can
reach 65 kA if the recommended Class fuses are used upstream.
Enclosed drives with the MCCB option have a 65 kA interrupting rating for 380–480 V. For 525–690 V, the interrupting rating is
30 kA for the N355 model and 50 kA for the others.
The table values are calculated using correction factors for a 40 °C (104 °F) ambient operating condition and using cables with a
minimum insulation rating of 90 °C (194 °F).
Table 69: Recommended Fuse Ratings for UL Installation, 380–480 V
Model
Fuse P/N (Mersen)
N110
A4J300
N132
A4J350
N160
A4J400
N200
A4J500
N250
A4J600
N315
AABY750
N355
A4BY800
N400
A4BY1000
N450
A4BY1000
N500
A4BY1100
N560
A4BY1200
Danfoss A/S © 2021.11
Fuse size
Rated cur-
rent [A]
3
425
3
500
3
500
4
630
4
800
4
800
4
1000
4
1000
Fuse P/N (Danfoss)
Maximum current
[A]
70CPE10965
300
70CPE10966
350
70CPE10522
400
70CPE10968
500
70CPE10523
600
70CPE10969
750
70CPE10974
800
70CPE10975
1000
70CPE10975
1000
70CPE10976
1100
70CPE10977
1200
Minimum pro-
Maximum fuse
spective SC cur-
rating F1 [A]
rent of the grid
[kA]
9.5
425
12
500
12
500
14
630
19
800
19
800
25
1000
25
1000
Maximum fuse rat-
ing F1 [A]
300
350
400
500
600
750
800
1000
1000
1100
1200
AQ262141314214en-000301 / 130R0880 | 105
Electrical Installation
Minimum volt-
Type F1
age rating [V]
690
gG/gL
690
gG/gL
690
gG/gL
690
gG/gL
690
gG/gL
690
gG/gL
690
aM
690
aM
Minimum voltage
Class F1
rating [V]
500
Class J
500
Class J
500
Class J
500
Class J
500
Class J
500
Class L
500
Class L
500
Class L
500
Class L
500
Class L
500
Class L