VLT® HVAC Drive FC 102
Operating Guide
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals; however, the USB
ground connection is not galvanically isolated from ground. Use only an isolated laptop as PC connection to the USB connector on
the drive.

10.6.2 STO Terminal XD2.19 (Terminal XD2.19 is Fixed PNP Logic)

STO Terminal XD2.19
(1)(2)
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Maximum voltage on input
Typical input current at 24 V
Typical input current at 20 V
Input capacitance
For more information about Terminal XD2.19 (Terminal 37 on the drive module) and Safe Torque Off, see the VLT
1
Operating Guide.
2
When using a contactor with a DC coil inside with STO, it is important to make a return way for the current from the coil when turning it off. This
can be done by using a freewheel diode (or, alternatively, a 30 V or 50 V MOV for quicker response time) across the coil. Typical contactors can be
bought with this diode.
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

10.6.3 Control Card, 24 V DC Output

Terminal number
Output voltage
Maximum load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.

10.6.4 Control Card, 10 V DC Output

Terminal number
Output voltage
Maximum load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

10.6.5 Digital Outputs

Programmable digital/pulse outputs
Terminal number
(1)
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
Can also be programmed as input.
1
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
162 | Danfoss A/S © 2021.11
Specifications
0–24 V DC
<4 V DC
>20 V DC
28 V DC
50 mA rms
60 mA rms
FC Series - Safe Torque Off
®
XD2.10, XD2.11
24 V +1, -3 V
200 mA
10.5 V ±0.5 V
XD2.14, XD2.15
Maximum error: 0.1% of full scale
AQ262141314214en-000301 / 130R0880
400 nF
XD2.6
15 mA
2
0–24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
12 bit