VLT® HVAC Drive FC 102
Operating Guide
Table 77: Wiring Configuration for Speed Up/Down
+24 V
XD2.10
+24 V
XD2.11
D IN
XD2.12
D IN
XD2.13
COM
XD2.18
D IN
XD2.14
D IN
XD2.15
D IN
XD2.16
D IN
XD2.17
D IN
XD2.19
Speed
Reference
Start (XD2.12)
Freeze ref (XD2.14)
Speed up (XD2.15)
Speed down (XD2.16)
Illustration 66: Speed Up/Down
120 | Danfoss A/S © 2021.11
Parameters
Function
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-13 Terminal 29 Digital Input
Parameter 5-14 Terminal 32 Digital Input
*=Deafult value
Notes/comments:
D IN 37 is an option.
Terminal 18 in the parameter title corresponds to terminal XD2.12 in the control compartment.
Terminal 27 in the parameter title corresponds to terminal XD2.14 in the control compartment.
Terminal 29 in the parameter title corresponds to terminal XD2.15 in the control compartment.
Terminal 32 in the parameter title corresponds to terminal XD2.16 in the control compartment.
Wiring Configuration Examples
Setting
[8] Start*
[19] Freeze Reference
[21] Speed Up
[22] Speed Down
AQ262141314214en-000301 / 130R0880