The motor heater option provides the ability to control the supply for the motor anti-condensation heater. The 24 V DC external
supply is connected to terminal -XD1.1 in the lower part of the cabinet. When the drive is not in run state, the control relay -QAM
changes the external supply to the -XDM output terminals. When the drive is in run state, the control relay disconnects the external
supply to the motor heater. The function is disabled when MCB –FCN is open.
-FCE
-XD1
L
1
6 A
Illustration 54: Motor Heater Control (A = Heater element, not included)
5.7.6.8 Insulation Monitor
Table 61: Auxiliary Function Type Codes
Character posi-
Code
tion
23–24
A5
AD
AG
AI
AJ
AK
AM
AN
AO
AR
AT
AU
AV
A8
AY
AZ
The insulation monitor option monitors the supply and insulation faults within the insulation level in an IT supply network with an
insulation monitor in the control compartment.
Danfoss A/S © 2021.11
A
-QAM
-XD4
Description
Insulation monitor
AC socket+cabinet light + insulation monitor
AC socket+cabinet light + extended I/O terminals + insulation monitor
AC socket+cabinet light + extended I/O terminals + cabinet heater + insulation monitor
AC socket+cabinet light + extended I/O terminals + motor heater control + insulation monitor
AC socket+cabinet light + extended I/O terminals + cabinet heater + motor heater control + insula-
tion monitor
AC socket+cabinet light + cabinet heater + insulation monitor
AC socket+cabinet light + cabinet heater + motor heater control + insulation monitor
AC socket+cabinet light + motor heater control + insulation monitor
Extended I/O terminals + insulation monitor
Extended I/O terminals + cabinet heater + insulation monitor
Extended I/O terminals + cabinet heater + motor heater control + insulation monitor
Extended I/O terminals + motor heater control + insulation monitor
Cabinet heater + insulation monitor
Cabinet heater + motor heater control + insulation monitor
Motor heater control + insulation monitor
-XDM
N
AQ262141314214en-000301 / 130R0880 | 93