To Display The Help Text In Case Of A Malfunction; Error Codes Of The Unit - Daikin EWYA004D2V3P Installer's Reference Manual

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA004D2V3P:
Table of Contents

Advertisement

15
|
Troubleshooting

15.4.1 To display the help text in case of a malfunction

15.4.2 Error codes of the unit

Installer reference guide
204
INFORMATION
See the service manual for:
The complete list of error codes
A more detailed troubleshooting guideline for each error
In case of a malfunction, the following will appear on the home screen depending
on the severity:
: Error
: Malfunction
You can get a short and a long description of the malfunction as follows:
1 Press the left dial to open the main menu and go to
Malfunctioning.
Result: A short description of the error and the error code is
displayed on the screen.
2 Press in the error screen.
Result: A long description of the error is displayed on the
screen.
= Compressor module,
Error code
7H-01
Water flow problem
7H-05
Water flow problem during heating/sampling
7H-06
Water flow problem during cooling/defrost
7H-07
Water flow problem. Pump deblocking active
7H-08
Pump abnormality during operation (pump
feedback)
80-00
Returning water temperature sensor problem
80-01
Entering water thermistor abnormality of
outdoor unit
81-00
Leaving water temperature sensor problem
81-01
Mixed water thermistor abnormality.
89-01
Heat exchanger freeze-up protection activated
during defrost (error)
89-02
Heat exchanger freeze-up protection activated
during heating / DHW operation. (warning)
89-03
Heat exchanger freeze-up protection activated
during defrost (warning)
89-05
Heat exchanger freeze-up protection activated
during cooling operation. (error)
= Hydro module
Description
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09