Daikin EWYA004D2V3P Installer's Reference Manual page 228

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA004D2V3P:
Table of Contents

Advertisement

6/12
Field settings table
Breadcrumb
Setting name
9.4.3
[8-03]
BSH eco timer
9.4.4
[4-03]
Operation
└─ Emergency
9.5.1
[4-06]
Emergency
9.5.2
[7-06]
HP forced OFF
Installer settings
9.7
[4-04]
Water pipe freeze prevention
└─ Benefit kWh power supply
9.8.2
[D-00]
Allow heater
9.8.3
[D-05]
Allow pump
9.8.4
[D-01]
Benefit kWh power supply
9.8.6
Allow electric heaters
9.8.7
Enable Room buffering
9.8.8
Limit setting kW
└─ Power consumption control
9.9.1
[4-08]
Power consumption control
9.9.2
[4-09]
Type
9.9.3
[5-05]
Limit
9.9.4
[5-05]
Limit 1
9.9.5
[5-06]
Limit 2
9.9.6
[5-07]
Limit 3
9.9.7
[5-08]
Limit 4
9.9.8
[5-09]
Limit
9.9.9
[5-09]
Limit 1
9.9.A
[5-0A]
Limit 2
9.9.B
[5-0B]
Limit 3
9.9.C
[5-0C]
Limit 4
9.9.D
[4-01]
Priority heater
9.9.F
[7-07]
BBR16 activation*
*BBR16 settings are only visible when the language of the user
interface is set to Swedish.
└─ Energy metering
9.A.1
[D-08]
Electricity meter 1
9.A.2
[D-09]
Electricity meter 2 / PV meter
└─ Sensors
9.B.1
[C-08]
External sensor
9.B.2
[2-0B]
Ext. amb. sensor offset
9.B.3
[1-0A]
Averaging time
└─ Bivalent
9.C.1
[C-02]
Bivalent
4P688017-1A - 2022.09
Range, step
Default value
R/W
20~95 min, step: 5 min
50 min
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
R/W
0: Manual
1: Automatic
2: Auto SH reduced/ DHW ON
3: Auto SH reduced/ DHW OFF
4: Auto SH normal/ DHW OFF
R/W
0: Disabled
1: Enabled
R/W
0: Continuous pump operation
1: Non continuous pump operation
2: OFF
R/W
0: No
1: Only BSH
2: Only BUH
3: All
R/W
0: No
1: Yes
R/W
0: No
1: Open
2: Closed
3: Smart Grid
R/W
0: No
1: Yes
R/W
0: No
1: Yes
R/W
0~20 kW, step: 0,5 kW
2 kW
R/W
0: No
1: Continuous
2: Inputs
3: Current Sensor
R/W
0: Amp
1: kW
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0: None
1: Booster Heater
2: Backup Heater
R/W
0: No
1: Yes
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
R/W
0: No
1: Outdoor
2: Room
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: No
1: 12 h
2: 24 h
3: 48 h
4: 72 h
R/W
0: NO
1: Yes
Installer setting at variance with
default value
Date
Value