Daikin EWYA004D2V3P Installer's Reference Manual page 167

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA004D2V3P:
Table of Contents

Advertisement

EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09
#
Code
[9.8.5]
N/A
[9.8.6]
N/A
[9.8.7]
N/A
[9.8.8]
N/A
Description
Restriction: Only applicable if [9.8.4]=Smart
grid.
Shows the Smart Grid operation mode sent by
the 2 incoming Smart Grid contacts.
Smart grid operation mode:
Free running
Forced off
Recommended on
Forced on
See also below table (Smart Grid operation
modes).
Restriction: Only applicable if [9.8.4]=Smart
grid.
To set if electrical heaters are allowed.
Allow electrical heaters:
No
Yes
Restriction: Only applicable in case of room
thermostat control, and if [9.8.4]=Smart grid.
To set if room buffering will be enabled.
Enable room buffering:
No: The extra energy from the photovoltaic
panels is NOT buffered in space heating circuit.
Yes: The extra energy from the photovoltaic
panels is buffered in the space heating/cooling
circuit (i.e. heat up or cool down the room).
Limit setting kW
Restriction: Only applicable if:
[9.8.4]=Smart grid.
There is no pulse meter (power meter) for
photovoltaic
panels
Electricity meter 2 = None)
Normally, when a pulse meter is available, the
following happens:
The pulse meter measures the power
produced by the photovoltaic panels.
The unit limits its power consumption during
the Smart Grid's "Recommended ON" mode to
only use the power provided by the
photovoltaic panels.
However, when the pulse meter is not available,
you can still limit the unit's power consumption
using this setting (Limit setting kW). This
prevents overconsumption and thus requiring
the use of power from the grid.
11
Configuration
|
available
([9.A.2]
Installer reference guide
167