11
|
Configuration
Installer reference guide
144
#
Code
[3.6]
[0-04]
[0-05]
[0-06]
[0-07]
Emitter type
For more information about Emitter type, see
#
Code
[3.7]
[2‑0D]
The setting of the emitter type has an influence on the space heating setpoint
range and the target delta T in heating as follows:
Description
Set weather-dependent cooling:
Note: There are 2 methods to set the weather
dependent curve. See
"11.5.2 2-points
4
curve" [
 124] and
"11.5.3 Slope-offset
4
curve" [
 125]. Both curve types require 4 field
settings to be configured according to the figure
below.
T t
[0-05]
[0-04]
[0-07]
[0-06]
T
:
Target
leaving
t
(additional zone)
T
: Outdoor temperature
a
[0-07]: Low outdoor ambient temperature.
10°C~25°C
[0-06]: High outdoor ambient temperature.
25°C~43°C
[0-05]: Desired leaving water temperature
when the outdoor temperature equals or drops
below
the
low
[9‑07]°C~[9‑08]°C
Note: This value should be higher than [0‑04]
as for low outdoor temperatures less cold
water is required.
[0-04]: Desired leaving water temperature
when the outdoor temperature equals or rises
above
the
high
[9‑07]°C~[9‑08]°C
Note: This value should be lower than [0‑05] as
for high outdoor temperatures colder water is
required.
"11.6.3 Main
Description
Emitter type:
0: Underfloor heating
1: Fancoil unit
2: Radiator
T a
water
temperature
ambient
temperature.
ambient
temperature.
4
zone" [
 133].
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09