Power consumption control
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1B – 2022.09
Power consumption control
See
"6  Application
guidelines"  [
functionality.
#
[9.9.1]
[4-08]
[9.9.2]
[4-09]
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
#
[9.9.3]
[5-05]
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
#
[9.9.4]
[5-05]
[9.9.5]
[5-06]
[9.9.6]
[5-07]
[9.9.7]
[5-08]
Limit when [9.9.1]=Continuous and [9.9.2]=kW:
#
[9.9.8]
[5-09]
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
#
[9.9.9]
[5-09]
[9.9.A]
[5-0A]
[9.9.B]
[5-0B]
[9.9.C]
[5-0C]
4
  24] for detailed information about this
Code
Power consumption control:
0 No: Disabled.
1 Continuous: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 Inputs: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
Type:
0 Amp: The limitation values are set in A.
1 kW: The limitation values are set in kW.
Code
Limit: Only applicable in case of full time
current limitation mode.
0 A~50 A
Code
Limit 1: 0 A~50 A
Limit 2: 0 A~50 A
Limit 3: 0 A~50 A
Limit 4: 0 A~50 A
Code
Limit: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Code
Limit 1: 0 kW~20 kW
Limit 2: 0 kW~20 kW
Limit 3: 0 kW~20 kW
Limit 4: 0 kW~20 kW
11
Configuration
|
Description
Description
Description
Description
Description
Installer reference guide
169