Reset Setup (Rst); Meter Information (Inf); Wi-Fi Setup (485 On/Off) Only Available For Dpm-C520W - Delta DPM-C320 Operation Manual

Multi-functional power meter
Table of Contents

Advertisement

D
5 20 /C5 20W /C32 0 Op era tio n M anu al
P M - C
4.2.8

Reset Setup (RST)

Default (DEF): Restore all the settings back to the defaults (including wireless settings).
Energy (ENG): Reset all the accumulated energy values and automatic energy values.
MaxMin (MM): Clear all maximum values and minimum value logs.
Alarm (ALA): Clear all the detected alarm logs.
Steps:
1.
Press BACK key to enter the setting page.
2.
Press UP and DOWN keys at the same time for 5 seconds to unlock the setting.
3.
Press NEXT key to see the setting option RST & INF.
4.
Press UP key to enter the reset (RST) setting page.
5.
Use UP and DOWN keys to select the reset options (DEF, ENG, MM and ALA).
6.
Press NEXT key to confirm the setting.
Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have
_4
completed or canceled the setting.
4.2.9

Meter Information (INF)

Model Name (MD): C520 or C520W
Firmware Version (FW): 1.XXXX
Date (DT): Firmware release date YYYY.MM.DD
Steps:
1.
Press BACK key to enter the setting page.
2.
Press UP and DOWN keys at the same time for 5 seconds to unlock the setting.
3.
Press NEXT key to see the setting option RST & INF.
4.
Press DOWN key to enter see the information (INF) page.
Note: You can go back to the previous setting item by pressing BACK key anytime, whether you have
completed or canceled the setting.

4.2.10 Wi-Fi Setup (485 ON/OFF) only available for DPM-C520W

Wi-Fi: When 485 is ON, Wi-Fi function is disabled. When 485 is OFF, Wi-Fi function is enabled.
Steps:
1.
Press BACK key to enter the setting page.
2.
See 485 ON or 485 OFF on the screen.
3.
Press NEXT key for 3 seconds to switch from 485 ON to 485 OFF.
4 - 8