D PM -C52 0 /C5 20W /C32 0 Op era tio n M anu al
1F
40032
20
40033
21
40034
22
40035
_5
23
40036
24
40037
34
40053
35
40054
36
40055
37
40056
38
40057
39
40058
3A
40059
3B
40060
5 - 4
4: Reset max./min. values
5: Reset SSID, PWD, IP to
factory default
(available for DPM-C520W)
6: Reset wireless module
(available for DPM-C520W)
Alarm – Over Current
0: Disable
Alarm enable
1: Enable
Pickup setpoint
(current value
0.000 – 99999.999
exceeding this value
triggers alarm)
Dropout setpoint
(current value below
0.000 – 99999.999
this value clears
alarm)
Alarm – Over Voltage L–L
0: Disable
Alarm enable
1: Enable
Pickup setpoint (line
voltage value
0.000 – 99999.999
exceeding this value
triggers alarm)
Dropout setpoint (line
voltage value below
0.000 – 99999.999
this value clears
alarm)
Alarm – Under Voltage L–L
0: Disable
Alarm enable
1: Enable
word
float
A
Reserved
float
A
word
float
V
Reserved
float
V
Reserved
word
2
R/W
4
R/W
4
R/W
2
R/W
4
R/W
4
R/W
2
R/W