Follett Horizon Elite 1412 Installation Instructions Manual page 4

Table of Contents

Advertisement

2.1
1.2
Condenser installation specifications
S-trap
required
CORPORATION
Easton Pennsylvania
MODEL
SERIAL NO
PART NO
SINGLE
FULL LOAD AMPS
VOLTS
HZ
PHASE
REFRIGERANT
MOTOR COMPRESSOR THERMALLY PROTECTED
CHARGE
OZ
DESIGN PRESSURE HIGH SIDE
LOW SIDE
PSIG
Stock Module Identification Plate
208264
MIN. BRANCH CIRCUIT AMPACITY
AMPS
UL
UL
Module No.
Product
MAX. BRANCH CIRCUIT FUSE SIZE
AMPS
R
C
R
NSF
MADE IN
THE USA
Service No.
EVAPORATOR
UNIT
Site layout:
• Outdoor ambient temperature range: –20 F to 120 F (–29 C to 49 C)
• Installation with condenser unit elevations above 20' (6.1 m) require an S-trap at the midpoint
of the rise and a P-trap at the top of the rise
• Maximum line rise must not exceed 35' (10.7 m)
• Maximum line set length must not exceed 100' (30.5 m)
• Low voltage control (24 Vac signal wire) must be connected
4
Low voltage control (24 Vac) required
100' max.
(30.5 m)
P-trap
required
P-trap
required
EVAPORATOR UNIT LEVEL
100' max.
(30.5 m)
CONDENSER UNIT
maximum
line rise
CONDENSER UNIT
REMOTE CONDENSING UNIT
+35'
(+10.7 m)
+20'
(+6.1 m)