Mounting SITRANS TS500 in the potentially explosive atmosphere
Zone 1/21 or 2/22 protrudes into zone 0/20 from left to right within the protective tube. The wall of the
protective tube is part of the separation element.
EPL (Equipment Protection Level) or device protection level
Figure 3-3
3.3

Mounting SITRANS TS300 in clamp-on design

Note
Measuring position
Only install on round pipes. Avoid an installation close to pipe elbows, sliders, valves, etc.
1. Determine the measuring position on the pipe.
2. Apply the thermal paste on the metal part of the temperature sensor.
3. For the standard design: Install the two sleeving parts to the pipe using two fixing screws.
For the clamp design: Mount the SITRANS TS300 using a fixing screw.
– If the process medium does not flow through the full cross-section of the pipe, mount the
SITRANS TS100/TS200/TS300/TS500/TSinsert/TSthermowell
Compact Operating Instructions, 06/2023, A5E03920348-AH
Zone 1 or 2
Zone 21 or 22
EPL Db
EPL Gb
Separation element: Flange and wall of the protective tube
Process
Zones 0 and 20
EPL Da
EPL Ga
Separation element between different zones and different device protection levels
temperature sensor on the bottom of the pipe.
3.3 Mounting SITRANS TS300 in clamp-on design
Installing/mounting
23