Siemens RDF210 Manual

Siemens RDF210 Manual

With lcd with 7-day time program for 2-pipe fan coil units, for use with compressors in dx type equipment

Advertisement

N3058en
10.01.2006
RDF210, RDF210.2, RDF210/IR, RDF210.2/IR
Room Temperature
Controllers with LCD
with 7-day time program
for 2-pipe fan coil units
for use with compressors in DX type equipment
Output for on / off valve actuator or 1-stage compressor
Operating Modes: Normal operation, Auto Timer (energy saving) and Standby
3-speed fan control: Automatic or manual
8 programmable timers
Adjustable commissioning and control parameters
Optional display of room temperature or setpoint
Minimum and maximum setpoint limitation
Operating voltage AC 230 V
Additional features of RDF210
Automatic heating / cooling changeover
Input for heating / cooling changeover or return air temperature sensor
Additional features of RDF210.2
Manual heating / cooling changeover
Optional
Infrared Remote Control (RDF210/IR, RDF210.2/IR)
3
RDF210...
Building Technologies
HVAC Products
058

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RDF210

  • Page 1 Additional features of RDF210 Automatic heating / cooling changeover Input for heating / cooling changeover or return air temperature sensor Additional features of RDF210.2 Manual heating / cooling changeover Optional Infrared remote control (RDF210/IR, RDF210.2/IR) Building Technologies N3058en HVAC Products 10.01.2006...
  • Page 2 Temperature control setpoint by delivering 2-position valve control commands or compressor output com- mands. With the RDF210, an external room temperature sensor (QAA32) or external return air temperature sensor (QAH11.1) can be used instead. The switching differential is 2 K in heating mode and 1 K in cooling mode (adjustable via parameters P08 and P09).
  • Page 3 Operating modes The following operating modes are available: In Normal operation, the controller maintains the setpoint, which can be adjusted via Normal operation buttons. The fan can be set to automatic or manual fan speed: Low, medium or high. The setpoint setting range can be limited to a minimum (P05) and maximum (P06). This Tip! helps prevent the waste of energy, thus saving costs.
  • Page 4 Control output Y12 delivers a control command which is inverted to the control command at output Y11 and which can be used for normally open valves. With the RDF210, the changeover between cooling and heating takes place either Heating / cooling...
  • Page 5 Whenever the fan starts from standstill, it starts with speed 3 for 1 second in order to Fan start guarantee a safe fan motor start (to overcome inertia and friction) In Auto Timer mode, the default fan mode is automatic. The fan mode can be changed Fan in Auto Timer to manual fan speed.
  • Page 6 The controller will leave the programmable timer setting mode if no button is pressed within 20 seconds. All changes made after the last press of button will not be saved. Press the button to sequentially review the 8 timers. View the timers Timers A1…A4 have the following default setting: Default timer setting Day/s...
  • Page 7 External sensor input B1-M With the RDF210, a return air / external room temperature sensor or heating / cooling changeover sensor can be connected to terminal B1-M. The function of this sensor input is determined by parameter P22. Sensor input B1-M is not galvanically separated from the AC 230 V mains supply.
  • Page 8 Using parameter P25, infrared remote control can be disabled. Control parameters With the RDF210 and RDF210.2, a number of control parameters can be readjusted to optimize the control performance. These parameters can also be set during operation without opening the unit. In the event of a power failure, all control parameter settings will be maintained.
  • Page 9 Press buttons simultaneously for 3 seconds. Release them and, within 2 seconds, press operating mode selector button 2 times. Then, the display will show “888“ during the reloading process. Control parameters of the RDF210 and RDF210.2 Para- Meaning Setting range Factory...
  • Page 10 RDF210 temperature sensor With manual heating / cooling changeover RDF210.2 Without input for sensor (only available in AP) Same as RDF210 plus infrared remote control RDF210/IR Same as RDF210.2 plus infrared remote control RDF210.2/IR (only available in AP) Equipment combinations...
  • Page 11 11 Button for setting time of day and weekday ( ) 12 Manual heating / cooling changeover ( ) (only with RDF210.2) 13 Auto timer program ( AUTO 14 Confirmation ( ) 15 Infrared receiver (only with RDF210…/IR) 11/15 Building Technologies Room Temperature Controllers N3058en HVAC Products...
  • Page 12 (also refer to “Setting the control parameters”). • Only with RDF210: Depending on the application, the heating / cooling mode must Heating / cooling mode be set via parameter P22.
  • Page 13 Temperature sensor QAH11.1, safety class II Voltage against earth AC 230 V Cable length max. 80 m (min. 1.5 mm Infrared receiver (only with RDF210…/IR) Transmission distance ≤ 7.5 m Orientation angle ≤ ± 30 ° Switching differential, adjustable from 0.5...4K...
  • Page 14 Changeover (QAH11.1+ ARG86.3) or Control output “Valve” AC 230 V (N.C., external room temperature sensor for normally open valves) (QAH11.1 / QAA32) * Only with RDF210 or RDF210/IR Measuring neutral for sensor Connection diagrams Return air temperature sensor (QAH11.1) Application:...
  • Page 15 Dimensions Controller Mounting base 28.7 94.85 3058Z05 ©2006 Siemens Switzerland Ltd. Subject to alteration 15/15 Building Technologies Room Temperature Controllers N3058en HVAC Products 10.01.2006...