Installing/mounting
3.4 Disassembly
4. Tighten the fixing screws (tightening torque 4 Nm).
5. Mount the vibration protection and tighten it manually.
– You can pull out the measuring insert by loosening the RTD recessed grip gland(s).
– Do not twist the enclosure.
– Only conduct the mounting work on the RTD recessed grip gland.
– Do not apply any force to the transmitter (e.g. when opening and closing the cover).
– Due to the seals being on the inside, the plug-in connectors are only suitable for an
3.4

Disassembly

Incorrect disassembly
The following risks may result from incorrect disassembly:
- Injury through electric shock
- Risk through emerging media when connected to the process
- Risk of explosion in hazardous area
In order to disassemble correctly, observe the following:
• Before starting work, make sure that you have switched off all physical variables such as
• If the device contains hazardous media, it must be emptied prior to disassembly. Make sure
• Secure the remaining connections so that no damage can result if the process is started
24
ambient temperature of up to 100 °C (212 °F).
WARNING
pressure, temperature, electricity etc. or that they have a harmless value.
that no environmentally hazardous media are released.
unintentionally.
SITRANS TS100/TS200/TS300/TS500/TSinsert/TSthermowell
Compact Operating Instructions, 06/2023, A5E03920348-AH