Technical data
7.1 Rated conditions
ΔT1 = Temperature rises due to the electronics used in the connection head BB0
ΔT2 = The temperature rises above the process temperature.
Table 7-3
Max. permissible Tamb, GAS, sensor range, TS100/200 or TS500 series
Maximum permissible ambient temperature / sensor range
SITRANS TS 100/200 or TS500 series with built-in measuring insert TS insert
Hazard through flammable gases:
Power supply Po (mW)
Fail-safe wattage limitation in accordance
with the device category 1 e.g., SIEMENS
temperature transmitter
SITRANS TH320/420
and or temperature display
 
Sensor type
Pt 100,
Type A, B, C
Pt 1000,
Type F, G
Thermocouple
Type
K, J, N, E, L, T,
R, S, U,
W = Type B
Table 7-4
Maximum permissible ambient temperature, DUST, connection area, TS500, head BA0, BB0, BC0, BM0, BP0
Maximum permissible ambient temperature Ty (°C), connection area, Zone 21
SITRANS TS500 series with built-in measuring insert TS insert
Connection head type: AG0, AH0, AU0, AV0, BA0, BB0, BC0
Risk of flammable dusts:
Type of installed connection head →
Degree of protection →
Maximum surface temperature of the connection head
Installed wattage of the electronics (W)
 
Temperature of
medium (°C)
48
Temperature
class
T1
T2
T3
T4
T6
T1
T2
T3
T4
T6
Distance between sensor
and connection head (mm)
 
 
0...≤37
≥37...≤100
Max. permissible process temperature (°C)
TS 500
under use
EPL Ga device
347
342
227
222
151
146
99
94
59
54
351
231
155
103
63
AH0, AV0
Ex t, Ex i
85 °C
0
1
Max. permissible process temperature (°C)
SITRANS TS100/TS200/TS300/TS500/TSinsert/TSthermowell
Compact Operating Instructions, 06/2023, A5E03920348-AH
 
0...≤37
TS 100/200, TS500
under use
EPL Gb, Gc device
435
285
190
125
75
439
289
194
129
79
BA0, BB0, BC0
AG0, AU0
Ex i
100 °C
0
1
0
 
≥37...≤100
428
278
183
118
68
Ex t, Ex i
150 °C
1