MAC3 HydroController HCW User Manual page 44

Table of Contents

Advertisement

del motor P1
48 Potencia
Potencia absorbida por la bomba (P1)
49 MaxCorr.Motor
Valor máximo de la protección
amperométrica.
50 Configur. Relays
Determina la función que se utilizará
para relè. El relé de alarma significa
para alarmas eléctricas e hidráulicas:
Vers. HC STD (MM,MT,TT 5.5hp):
R1:Alarm (Relé de alarma)
R1:Run (Relé de partida)
R1:Remote Alarm (relé de alarma en el
R1:Booster (Relé de la bomba booster)
Vers. HC ADV (MM,MT,TT 5.5hp):
R1:Alm R2:Run (relè alarma, relè de
R1:Alm R2:RemAlm (relè alarma, relé
R1:A R2:R R3:RA (relè alarma, relè de
R1:A R2:R R3:B1 (relè alarma, relè de
R1:A R2:B1 R3:B2 (relè alarma, relè
R1:R R2:B1 R3:B2 (relè de partida, relè
R1,R2,R3:Booster (relè booster1,2,3)
51 Aument.P.Booster
Aumento de la presión del sistema
cuando el booster está activo (default
+2.9 psi)
52 Autoc TiempoVida
Tiempo de la vida de uso de un
autoclave (minutos, segundos)
53 Autoc TiempoVida
Tiempo de la vida de uso de un
autoclave (días, horas)
54 Pico de corr.
Establece el pico máximo de corriente
detectada , después de que la
protección se ajusta: "Pico de
corriente". El pico de corriente se puede
visualizar durante 5 segundos en el
menú principal pulsando la tecla
55 Control remoto
Si ON, el inverter está en standby y
espera a un comando externo para
iniciar (p. Ej. interruptor flotante)
56 Potencia Total
Potencia Total de energía absorbida en
la configuración de Multi-bombas
57 Motores Activos
Número de motores activos en la
configuración de Multi-bombas
58 MinMantenimiento
Tiempo de inactividad de forma
continua durante 24 horas. Si la bomba
no está en OFF durante el tiempo
establecido, después de 24 horas, la
pantalla muestra "Perdidas"
59 Historial Fallas
Ver los últimos 5 errores del sistema.
El primer error que se muestra es el
último memorizado por el inversor.
Con la tecla - podrás ver los otros 4
errores más antiguos.
Istruzioni-HCMMMTTT-09022023 (Cod.620100007 Rev.16) EsEng (USA) MAC3.doc
control remoto)
partida)
de alarma en el control remoto)
partida, relé de alarma en el control)
partida, relè booster)
booster1, relè booster2)
booster1, relè booster2)
cuando la bomba arranca.
Power
Power absorbed by the pump (P1)
Max motor current Threshold of the amperometric
protection.
Relays Configur.
Determines the function to be assigned
to Relay. The alarm relay means for
both electric and hydraulic alarms:
Vers. HC STD (MM,MT,TT 5.5hp):
R1: Alarm (Alarm relay)
R1: Run (Run relay)
R1:Remote Alarm (alarm relay on
remote control)
R1: Booster (booster pump command
relay)
Vers. HC ADV (MM,MT,TT 5.5hp):
R1:Alm R2:Run (Alarm relay , run
relay)
R1:Alm R2:RemAlm (Alarm relay,
alarm relay on remote control)
R1:A R2:R R3:RA (Alarm, Run, booster
pump command relay, alarm relay
on remote control)
R1:A R2:R R3:B1 (Alarm, Run, booster
pump command relay)
R1:A R2:B1 R3:B2 (Alarm, booster1,
booster2 pump command relay)
R1:R R2:B1 R3:B2 (Run,booster1,
booster2 pump command relay)
R1,R2,R3:Booster (booster1,2,3 pump
command relay)
Inc Pres Booster
Increase the system pressure when the
booster is on (default +2.9 psi)
Autoc Life Time
Autoclave usage time (min, sec)
Autoc Life Time
Autoclave usage time (day, hour)
Peak Current
Sets the maximum peak current
threshold for the "High peak curr"
alarm.The current can be displayed for
5 seconds from the main menu
pressing
Remote enable
If ON,the inverter is in STANDBY and
wait external command to start (eg.
float switch)
Total Power
Total power absorbed in multipump
configuration
Running motor
Active pumps in mutipump
configuration
MinHold
Continuous pump off time within a 24
hour range (default 45min). If the
pump is not OFF for the set time, after
24 hours, the display shows "Leakage"
Fault history
View the last 5 system errors.
The first error displayed is the last one
memorized by the inverter. With the -
key you can view the other 4 oldest
errors.
key when the pump starts.
44