Installer Manual Fleck 2910 - NXT - Programming
6.5.
Master programming mode
Note
As soon as programming mode is entered, all parameters can be displayed or set to suit the
needs. Depending on the current programming, some functions will not be displayed or will
not be changeable.
Note
If none of the buttons are pushed for 5 minutes in the Programming mode, or if there is a
power failure, the controller returns to Service mode without saving.
Mandatory
In order to store the new settings in the programming mode, it is necessary to go through
all the parameters.
6.5.1. Master programming mode chart
Parameter
ENGLISH
FRANCAIS
LANGUAGE
DEUTSCH
ITALIANO
ESPANOL
SYSTEM TYPE
VALVE ADDRESS
58 / 114
Options
Definition
English
French
German
Spanish
4
Single unit
5
Parallel interlock
Parallel series
6
regeneration
7
Alternating
9
Alternating
14
Multiple demand valves
#1
First control valve
Second control valve
#2
(default)
#3
Third control valve
#4
Fourth control valve
Italian
1 unit.
2 to 4 units.
2 units.
2 to 4 units.
This screen will not be displayed for
system type 4.
Note