10. SOFTWARE UPDATE AND CONFIGURATION

10.1 Smart Key: operating instructions

start
mode
Fig. 10.a
Programming the Smart Key via Personal Computer
The operating modes described in the table below can be confi gured
using a program on the PC. The program can also load the software to the
key or transfer logged data from the controller to disk.
Type Function
Update software from key to pRack
B
(BIOS, application, parameters, etc.)
Copy software from pRack to pRack
C*
(BIOS, application, parameters, etc.)
*: Default mode
The key is factory-programmed in read/write mode (type C) so that it can
be used immediately to transfer software from one controller to another.
When the key is connected to the personal computer, the symbols have
the following meanings:
Flashing
Waiting for connection to PC
Alternating When connected to PC indicates data transfer in progress
The programming key is compatible starting from BIOS version 3.43 and
BOOT version 3.01. For more detailed information on programming the
key, see the pRack Manager program manual.
Using the Smart Key with the pRack
Switch off the pRack, remove any peripherals connected in the pLAN
and plug the key into the telephone connector on the controller. When
switching on again, all the symbols light up momentarily and the buzzer
emits a beep. A few seconds later the key becomes operational. During
this period the symbols
programming mode and the start button lights up steadily. Press the
button to start data transfer.
Important: If the key is type B or C pressing the start button will
immediately delete the software already loaded on the pRack.
Important: Do not remove the key while data is being transferred
to the key itself, as the fi le being transferred will be lost and the
corresponding space will not be restored. To restore the original capacity
all the fi les will need to be deleted. If the key is type "C" , simply perform a
new application read operation.
Copyright HPL March 2021
start
mode
Mode button
Disabled
Switches the key from write
mode to read mode
Tab. 10.a
will fl ash. The controller then enters
Meanings of Buttons/Symbols
Flashing: The key is connecting to the pRack. During this phase,
which may last a few seconds, the start button is disabled.
start
Flashing: The key has detected the pRack and is checking the
access rights.
On steady: Pressing the start button will start writing the
start +
software to the pRack.
On steady: Pressing the start button will start reading the
start +
software from the pRack.
On steady: Pressing the start button will start reading the logs
start +
from the pRack.
On steady: In case of C, pressing the button for 1 second
mode
switches from read to write.
If the key is type C, pressing the "mode" button for 1 second switches
from read to write. The symbols
(read logs) refl ect the selected status. If the key is not type "C", the
"mode" button is disabled and off . The "start" button starts the read or
write operation, indicated by the fl ashing of the corresponding symbol (
or
) at a frequency proportional to the progress of the operation.
When the operation is completed, the buzzer will sound intermittently
for 2 seconds. Pressing the "start" button again will make the buzzer
sound without repeating the operation. To repeat the operation, the key
must fi rst be unplugged. In case of error the symbol will light up together
with the other LEDs. The following table can help you fi nd the cause of
the problem.
Errors before pressing the START button
Symbols fl ashing
+
+
Symbols steady Password error
+mode
Symbols fl ashing Type of key is incompatible.
+mode
Symbols steady The key is missing one or more
+
Symbols steady
+ fl ashing start
+
+start
Symbols steady
+ fl ashing mode
+
+mode
Symbols steady No logged data present on the pRack.
+
+
Steady
Errors after pressing the START button
Symbols fl ashing
and buzzer sounding
+start+
+buzzer
intermittently
Symbols fl ashing
and buzzer sounding
+start+
+buzzer
intermittently
Symbols fl ashing
and buzzer sounding
+start+
+buzzer
intermittently
Symbols steady +
+
+
fl ashing
Steady
+
Flashing
87
Page 136 of 172
(write to pRack),
(read from pRack),
Communication error: No response
from the pRack or: Key fi rmware
version is incompatible.
required fi les (memory empty; no kit
for the type of pRack connected).
Incompatibility between the software
on the key and the pRack HW.
Incompatibility between pRack
application and HW (application size).
Type of key not programmed.
Write operation failed.
Read operation failed.
Read logs operation
failed.
Incompatibility between
log confi guration and
pRack HW (no dedicated
fl ash memory). This
error does not prevent
writing other fi les.
Insuffi cient space to
read logs.
Generic error
P4114S Rev 03
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
ENG
Tab. 10.b
Tab. 10.c
Tab. 10.d