WARNING:
Although every attempt to ensure parameters are correct, it is ultimately the Installer and or the Commissioning Engineers responsibility to check and ensure the correct parameters have been programmed and tested.
Mask
Index
Cab01
L1
Compressors regulation type
Cab01
L1
Compressors control mode
Cab02
L1
Minimum suction setpoint
Cab02
L1
Maximum suction setpoint
Cab03
L1
Suction setpoint
Cba04
L1
uct. - Regulation type (P - P+I - PID)
Cba04
L1
uct. - Integral time
Cba05
L1
Suction differential
Cab08
L1
Increasing zone differential for compressors regulation (neutral zone)
Cab08
L1
Decreasing zone differential for compressors regulation (neutral zone)
Cab12
L1
Compressors neutral zone minimum complete activation time (neutral zone)
Cab12
L1
Compressors neutral zone maximum complete activation time (neutral zone)
Cab13
L1
Compressors neutral zone minimum complete deactivation time (neutral zone)
Cab13
L1
Compressors neutral zone maximum complete deactivation time (neutral zone)
Cab20
--
Cab20
--
Cad08
L1
Enable floating suction setpoint compensation
Cad09
L1
Floating suction maximum setpoint
Cad09
L1
Floating suction minimum setpoint
Cad10
L1
Floating suction maximum delta admitted
Caf02
L1
Compressors type
Caf02
L1
Number of compressors
Caf04
L1
Suction refrigerant type
Caf10
L1
Compressors rotation type
Caf11
L1
Sequence of load unloader
Caf15
L1
Compressors modulating device type
Caf90
L1
Have compressors different size? {0=Equal - 1=Different}
Caf90
L1
Have compressors different number of valves? {0=Equal - 1=Different}
Caf91
L1
Compressors size 1
Caf91
L1
Compressors size 2
Caf91
L1
Compressors size 3
Caf91
L1
Compressors size 4
Caf92
L1
Stages configuration for compressor size 1
Caf92
L1
Stages configuration for compressor size 2
Caf92
L1
Stages configuration for compressor size 3
Caf92
L1
Stages configuration for compressor size 4
Caf16
L1
Compressors inverter minimum frequency
Caf16
L1
Compressors inverter maximum frequency
Cag01
L1
Compressors inverter minimum voltage
Cag01
L1
Compressors inverter maximum voltage
Cag01
L1
Compressors inverter nominal frequency
Cag01
L1
Compressors inverter nominal power
Cag02
L1
Compressors inverter rising time
Cag02
L1
Compressors inverter falling time
Cag05
L1
Regulation value in case of all regulation probe fault
Cad05
L1
Function for setpoint compensation by digital input enabled (suct/cond)
Ffa04
--
************
--
L1 - FANS
--
************
--
Dab01
L1
Fans regulation type
Dab01
L1
Fans control mode
Dab02
L1
Minimum condensing setpoint
Dab02
L1
Maximum condensing setpoint
Dab03
L1
condensing setpoint
Dab04
L1
Fan can work only when at least one compressor work
Dab06
L1
ond. - Regulation type (P - P+I - PID)
Dab06
L1
ond. - Integral time
Dab14
L1
condensing neutral zone minimum complete activation time (neutral zone)
Dab14
L1
condensing neutral zone maximum complete activation time (neutral zone)
Dab15
L1
condensing neutral zone minimum complete deactivation time (neutral zone)
Dab15
L1
condensing neutral zone maximum complete deactivation time (neutral zone)
Dad05
L1
Enable floating condensing setpoint compensation
Dad06
L1
Floating condensing offset
Daf01
L1
Number of fans
Daf04
L1
condensing refrigerant type
Daf05
L1
Fans rotation type
Dag01
L1
Fans modulating device type
Dag02
L1
Fan inverter minimum voltage
Dag02
L1
Fan inverter maxiimum voltage
Dag02
L1
Fan inverter minimum activation
Dag02
L1
Fan inverter maxiimum activation
Dag13
L1
Speed-up procedure duration
Dab05
L1
Setup for fans regulation cutoff
************
--
L1 - ALARMS
--
************
--
Cae04
L1
Compressors alarm 1 delay
Cae04
L1
Alarm1 of compressor start delay
Cae04
L1
Compressor alarm 1 type(0.Auto 1.Manual)
Cae04
L1
Compressor alarm 1 priority (0=Light - 1=Serious)
Cae07
L1
Compressors alarm 2 delay
Cae07
L1
Alarm 2 of compressor start delay
Cae07
L1
Compressor alarm 2 type(0.Auto 1.Manual)
Cae07
L1
Compressor alarm 2 priority (0=Light - 1=Serious)
Cae10
L1
Compressors alarm 3 delay
Cae10
L1
Alarm 3 of compressor start delay
Cae10
L1
Compressor alarm 3 type(0.Auto 1.Manual)
Cae10
L1
Compressor alarm 3 priority (0=Light - 1=Serious)
Cae13
L1
Compressors alarm 4 delay
Cae13
L1
Alarm 4 of compressor start delay
Cae13
L1
Compressor alarm 4 type(0.Auto 1.Manual)
Cae13
L1
Compressor alarm 4 priority (0=Light - 1=Serious)
Cae16
L1
Compressors alarm 5 delay
Cae16
L1
Alarm 5 of compressor start delay
Copyright HPL March 2021
Description
Value
UOM
Type
0 PROPORTIONAL BAND
0 PRESSURE
7 barg
90 barg
19 barg
1 PROP. + INT.
120 s
3 barg
0 barg
0 barg
5 s
30 s
10 s
60 s
--
--
--
--
1 YES
70 barg
19 barg
40
1 SCROLL
1 -
10 R744
1 FIFO
2 CpppCppp
1 INVERTER
0 NO
0 NO
10
10
10
10
0
100
0
100
0
100
0
100
30 Hz
60 Hz
0
10
50 Hz
10
120 s
20 s
0 %
0 NO
--
--
--
--
--
--
--
--
0 PROPORTIONAL BAND
1 TEMPERATURE
18 °C
30 °C
23 °C
1 YES
0 PROPORTIONAL
0 s
5 s
30 s
10 s
60 s
1 °C
3
1 --
10 --
1 FIFO
1 0-10V INVERTER-EC FANS
0 V
100 V
5 kW
100 kW
5 s
20
--
--
--
--
--
--
0 s
0 s
0 AUT.
1 SERIOUS
0 s
0 s
0 AUT.
1 SERIOUS
0 s
0 s
0 AUT.
1 SERIOUS
0 s
0 s
0 AUT.
1 SERIOUS
0 s
0 s
Page 146 of 172