Cae16
L1
Compressor alarm 5 type(0.Auto 1.Manual)
Cae16
L1
Compressor alarm 5 priority (0=Light - 1=Serious)
Cae19
L1
Compressors alarm 6 delay
Cae19
L1
Alarm 6 of compressor start delay
Cae19
L1
Compressor alarm 6 type(0.Auto 1.Manual)
Cae19
L1
Compressor alarm 6 priority (0=Light - 1=Serious)
Cae22
L1
Compressors alarm 7 delay
Cae22
L1
Alarm 7 of compressor start delay
Cae22
L1
Compressor alarm 7 type(0.Auto 1.Manual)
Cae22
L1
Compressor alarm 7 priority (0=Light - 1=Serious)
Cae24
L1
Relative suction setpoint high alarm
Cae24
L1
High suction pressure alarm threshold
Cae25
L1
High suction pressure alarm differential
Cae25
L1
High suction pressure alarm delay
Cae26
L1
Relative suction setpoint low alarm
Cae26
L1
Low suction pressure alarm threshold
Cae27
L1
Low suction pressure alarm differential
Cae27
L1
Low suction pressure alarm delay
Cae29
L1
Super Heat configuration
Cae29
L1
Low superheat alarm threshold
Cae29
L1
Low superheat alarm differential
Cae29
--
Cae29
L1
Superheat Alarm manual or automatic reset
Cae29
L1
Low superheat alarm delay
Cae31
L1
Discharge threshold setpoint
Cae31
L1
Discharge threshold differential
Cae31
L1
Enable the switch off of the compressor when its high discharge temperature alarm occurs
Cae36
--
Cae36
L1
High discharge pressure alarm threshold
Cae37
L1
High discharge pressure alarm differential
Cae37
L1
High discharge pressure alarm delay
Gca01
L1
Common HP alarm type
Gca01
L1
High common condensing pressure delay
Gca02
L1
Low common condensing pressure start delay
Gca02
L1
Low common condensing pressure delay
Gca03
L1
Time for lock compressor during low pressure
Gca03
L1
Number of tries before become manual
Gba01
L1
Enable high condensing pressure prevent
Gba01
--
Gba02
--
Gba02
--
Gba02
--
Gba06
--
Gba06
--
Gba06
--
************
--
L2 - COMPRESSORS --
************
--
Cbb01
L2
Compressors regulation type
Cbb01
L2
Compressors control mode
Cbb02
L2
Minimum suction setpoint
Cbb02
L2
Maximum suction setpoint
Cbb03
L2
Suction setpoint
Cba04
L2
uct. - Regulation type (P - P+I - PID)
Cba04
L2
uct. - Integral time
Cbb05
L2
Suction differential
Cbb08
L2
Increasing zone differential for compressors regulation (neutral zone)
Cbb08
L2
Decreasing zone differential for compressors regulation (neutral zone)
Cbf11
L2
Sequence of load unloader
Cbb12
L2
Compressors neutral zone minimum complete activation time (neutral zone)
Cbb12
L2
Compressors neutral zone maximum complete activation time (neutral zone)
Cbb13
L2
Compressors neutral zone minimum complete deactivation time (neutral zone)
Cbb13
L2
Compressors neutral zone maximum complete deactivation time (neutral zone)
Cbb20
--
Cbb20
--
Cbd08
L2
Enable floating suction setpoint compensation
Cbd09
L2
Floating suction maximum setpoint
Cbd09
L2
Floating suction minimum setpoint
Cbd10
L2
Floating suction maximum delta admitted
Cbf02
L2
Compressors type
Cbf02
L2
Number of compressors
Cbf04
L2
Suction refrigerant type
Cbf10
L2
Compressors rotation type
Cbf15
L2
Compressors modulating device type
Cbf40
L2
Have compressors different size? {0=Equal - 1=Different}
Cbf40
L2
Have compressors different number of valves? {0=Equal - 1=Different}
Cbf41
L2
Compressors size 1
Cbf41
L2
Compressors size 2
Cbf41
L2
Compressors size 3
Cbf41
L2
Compressors size 4
Cbf42
L2
Stages configuration for compressor size 1
Cbf42
L2
Stages configuration for compressor size 2
Cbf42
L2
Stages configuration for compressor size 3
Cbf42
L2
Stages configuration for compressor size 4
Cbf16
L2
Compressors inverter minimum frequency
Cbf16
L2
Compressors inverter maximum frequency
Cbg01
L2
Compressors inverter minimum voltage
Cbg01
L2
Compressors inverter maximum voltage
Cbg01
L2
Compressors inverter nominal frequency
Cbg01
L2
Compressors inverter nominal power
Cbg02
L2
Compressors inverter rising time
Cbg02
L2
Compressors inverter falling time
Cbg05
L2
Regulation value in case of all regulation probe fault
Cbd05
L2
Function for setpoint compensation by digital input enabled (suct/cond)
************
--
L2 - FANS
--
************
--
Dbb01
L2
Fans regulation type
Copyright HPL March 2021
0 AUT.
1 SERIOUS
0 s
0 s
0 AUT.
1 SERIOUS
0 s
0 s
0 AUT.
1 SERIOUS
0 ABSOLUTE
50
3
300 s
0 ABSOLUTE
7
1
120 s
2 ONLY ALARM
1
1
--
--
1 AUTO.
180 s
130
30
1 YES
--
--
105
5
0 s
0 AUT.
1 s
60 s
20 s
120 min
5 --
1 YES
--
--
--
°C
--
°C
--
s
--
°C
--
°C
--
s
--
--
--
--
--
--
1 NEUTRAL ZONE
0 PRESSURE
0
40
12
0 PROP. + INT.
0 s
0
0
0
2 CpppCppp
15 s
90 s
30 s
180 s
--
--
--
--
0 NO
40
0
1
0 RECIPROCATING
3 -
10 --
1 FIFO
0 NONE
0 NO
0 NO
10
10
10
10
0
100
0
100
0
100
0
100
30 Hz
60 Hz
0
10
50 Hz
10
20 s
20 s
0 %
0 NO
--
--
--
--
--
--
0 PROPORTIONAL BAND