1. Make sure all power supplies power cord are properly installed. Check if AC power is stable.
• C9 : Throttle_OUT
Node is notified of PSU Over-current condition. Node could enter power throttling state and perfomrance
could be affected.
Severity
Non-Recoverable
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Make sure all power supplies power cord are properly installed. Check if AC power is stable.
2. Make sure that all power supplies are in healthy condition.
3. Make sure that all nodes are properly installed and are not in fault condition.
4. Make sure that the node configuration meet the power limitation of current power supply
configuration.
• CA : Chassis_Cap_Low
User input chassis level capping value is lower than the lowest capping value possible for this particular
chassis, so the user input capping value may not be maintained.
Severity
Warning
Serviceable
Automatically notify support
User Action
1. Set capping value within suggested range.
• CB : Node_Cap_Low
User input node level capping value is lower than the lowest capping value possible for this particular
node, so the user input capping value may not be maintained.
Severity
Warning
Serviceable
Automatically notify support
User Action
1. Set capping value within suggested range.
• CC : USB Key Missing
FPC detects that the onboard USB device is broken or not installed.
Severity
Critical
Serviceable
244
ThinkSystem SD650 Dual Node DWC Tray and NeXtScale n1200 DWC Enclosure Messages and Codes Reference