c. If device is not recognized, reconfiguring slot to Gen1 or Gen2 may be required. Gen1/Gen2
settings can be configured via F1 Setup -> System Settings -> Devices and I/O Ports ->PCIe
Gen1/Gen2/Gen3 Speed Selection, or the OneCLI utility.
d. If a PCIe error has also been reported on a second slot within the same node, ensure steps a, b,
and c above are also performed for that adapter before proceeding.
3. If the problem persists, collect Service Data logs and contact Lenovo Support.
• FQXSFIO0012M: A PCIe system error has occurred on Bus [arg1] Device [arg2] Function [arg3].
The Vendor ID for the device is [arg4] and the Device ID is [arg5]. The Physical slot number is [arg6].
Severity: Error
Parameters:
[arg1]: Bus [arg2]: Device [arg3]: Function [arg4]: VID [arg5]: DID [arg6]: Instance number
User Action:
Complete the following steps:
1. Check Lenovo Support site for an applicable device driver, firmware update, version of service
information for this product or other information that applies to this error. Load new device driver and
any required firmware updates.
2. If this device and/or any attached cables were recently installed, moved, serviced or upgraded.
a. Reseat Adapter and any attached cables.
b. Reload Device Driver.
c. If device is not recognized, reconfiguring slot to Gen1 or Gen2 may be required. Gen1/Gen2
settings can be configured via F1 Setup -> System Settings -> Devices and I/O Ports ->PCIe
Gen1/Gen2/Gen3 Speed Selection, or the OneCLI utility.
d. If a PCIe error has also been reported on a second slot within the same node, ensure steps a, b,
and c above are also performed for that adapter before proceeding.
3. If the problem persists, collect Service Data logs and contact Lenovo Support.
Note: The solution for this error may involve a system board replacement. If TPM encryption has
been enabled, back up TPM Encryption Recovery Key.
• FQXSFIO0013I: The device found at Bus [arg1] Device [arg2] Function [arg3] could not be
configured due to resource constraints. The Vendor ID for the device is [arg4] and the Device ID is
[arg5]. The physical slot number is [arg6].
Severity: Warning
Parameters:
[arg1]: Bus [arg2]: Device [arg3]: Function [arg4]: VID [arg5]: DID [arg6]: Instance number
User Action:
Complete the following steps:
1. If this PCIe device and/or any attached cables were recently installed, moved, serviced or upgraded,
reseat adapter and any attached cables.
2. Check Lenovo Support site for any applicable service bulletin or UEFI or adapter firmware update
that applies to this error.(NOTE: It may be necessary to disable unused option ROMs from UEFI F1
setup, OneCLI utility, or using adapter manufacturer utilities so that adapter firmware can be
updated.)
3. Move the adapter to a different slot. If a slot is not available or error recurs, replace the adapter.
4. If the problem persists, collect Service Data logs and contact Lenovo Support.
150
ThinkSystem SD650 Dual Node DWC Tray and NeXtScale n1200 DWC Enclosure Messages and Codes Reference