Toshiba MMY-MUP0801HT8P-TR Service Manual page 63

Air conditioner multi type, super modular multi system-u smms-u, outdoor
Table of Contents

Advertisement

No.
Item
3
Room temp.
2) Using the Item code 06, the setup temperature in heating
control
(Continued)
4
Automatic
1) Based on the difference between TA and Ts, the opera-
capacity control
5
Automatic
1) The judgment of selecting COOL/HEAT is carried out as
cooling/heating
control
2) For the automatic capacity control after judgment of
3) For temperature compensation of room temp. control in
Outline of specifications
operation can be compensated.
Setup data
Setup temp. compensation
Setting at shipment
Model
Floor standing cabinet, Floor standing concealed,
Floor standing
Other models
tion capacity is determined by the outdoor unit.
COOL
TA
(˚C)
+2
SD
SB
+1
S9
S7
Ts
S5
S3
S0
–1
shown below. When +1.5 exceeds against Tsh
10 minutes and after thermostat OFF, heating operation
(Thermostat OFF) exchanges to cooling operation.
Description in the parentheses shows an example of
cooling ON/OFF.
TA
Cooling
(˚C)
+1.5
Tsc
or
Tsh
(Cooling OFF)
-1.5
When –1.5 lowers against Tsc 10 minutes and after
thermostat OFF, cooling operation (Thermostat OFF)
exchanges to heating operation.
cooling/heating, see Item 4.
automatic heating, see Item 3.
0
2
4
+0˚C
+2˚C
+4˚C
+6˚C
Set data
0
2
HEAT
TA
(˚C)
+1
S3
S0
S5
Ts
S7
S9
–1
SB
SD
–2
SF
(Cooling ON)
Heating
- 63 -
Remarks
Shift of return air
temperature in heating
operation
6
Except while sensor of
the remote controller is
controlled
(Code No. [32], "0001")
Ts: Setup temp.
TA: Room temp.
∗ For SHRM only
Tsc: Setup temp. in
cooling operation
Tsh: Setup temp. in
heating operation +
temp. compensation
of room temp. control