Toshiba MMY-MUP0801HT8P-TR Service Manual page 186

Air conditioner multi type, super modular multi system-u smms-u, outdoor
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
00:
Capacity over
01-:
No. of units
connected
E16
E16
E18
00:
No header unit
02:
Two or more
E19
E19
header units
01:
Connection of
outdoor unit
from other line
E20
E20
02:
Connection of
indoor unit
from other line
E23
E23
E25
E25
Address of
outdoor unit
from which
signal is not
received
normally
E26
E26
Location
Description
System status
of
detection
I/F
Too many
All stop
indoor units
connected
Indoor unit
Trouble in
Stop of
communication
corresponding
between indoor
unit
header and
follower units
I/F
Trouble in
All stop
number of
outdoor header
units
I/F
Connection to
All stop
other line found
during
automatic
address setting
I/F
Outdooroutdoor
All stop
communication
transmission
trouble
I/F
Duplicated
All stop
follower outdoor
address
I/F
Signal lack of
All stop
outdoor unit
- 186 -
Check code detection
Check items (locations)
condition(s)
• Combined capacity of
• Check capacities of indoor
indoor units is too large.
units connected.
• Check combined HP
Note:
capacities of indoor units.
If this code comes up
• Check HP capacity
after backup setting for
settings of outdoor units.
outdoor unit failure is
• Check No. of indoor units
performed, perform "No
connected.
capacity over detected"
• Check for failure in outdoor
setting.
P.C. board (I/F).
<"No capacity over detected"
setting method>
Turn on SW103 / Bit 3 on I/F
P.C. board of outdoor header
unit.
For Cooling Only model,
this check code is not
displayed even if it exceeds
the combined capacity of
indoor units.
• More than 128 indoor units
are connected.
Periodic communication
• Check remote controller
between indoor header and
wiring.
follower units cannot be
• Check indoor power supply
maintained.
wiring.
• Check P.C. boards of
indoor units.
The outdoor unit which
• There are more than one
turned on SW101 and the
outdoor header units in
bit 1 of the interface
one line.
P.C.board is set to Header
• There is no outdoor header
unit.
unit in one line.
• Check SW101 bit 1 of
follower outdoor unit.
• Check connection of
indoor-outdoor
communication line.
• Check for failure in outdoor
P.C. board (I/F).
Check whether the outdoor
Equipment from other line is
unit of other systems or the
found to have been
indoor unit is connected to
connected when indoor
Uv (U1/U2) line or Uc
automatic address setting is
(U5/U6) line.
in progress.
Signal cannot be transmitted
• Check power supply to
to other outdoor units for at
outdoor units. (Is power
least 30 seconds
turned on?)
continuously.
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for failure in outdoor
P.C. board (I/F).
• Check termination
resistance setting for
communication between
outdoor units.
There is duplication in
Note:
outdoor addresses set
Do not set outdoor
manually.
addresses manually.
Outdoor unit initially
• Backup setting is being
communicating normally
used for outdoor units.
fails to return signal for
• Check power supply to
specified length of time.
outdoor unit. (Is power
turned on?)
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for failure in outdoor
P.C. board (I/F).