Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
F16
F16
F23
F23
F24
F24
F29
F31
F31
1∗: Compressor
1 side
2∗: Compressor
2 side
H01
H01
1∗: Compressor
1 side
H02
H02
2∗: Compressor
2 side
1∗: Compressor
1 side
2∗: Compressor
H03
H03
2 side
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
Location
Description
System status
of
detection
I/F
Outdoor
All stop
pressure
sensor wiring
trouble (Pd, Ps)
I/F
Ps sensor
All stop
trouble
I/F
Pd sensor
All stop
trouble
Indoor unit
Other indoor
Stop of
trouble
corresponding
unit
I/F
Outdoor
All stop *1
EEPROM
trouble
Compressor
Compressor
All stop
P.C. board
breakdown
Compressor
Compressor
All stop
P.C. board
trouble (lockup)
MG-CTT trouble
Compressor
Current
All stop
P.C. board
detection
circuit trouble
- 189 -
Check code detection
Check items (locations)
condition(s)
Readings of high-pressure
• Check connection of high-
Pd sensor and low-pressure
pressure Pd sensor
Ps sensor are switched.
connector.
Output voltages of both
• Check connection of low-
sensors are zero.
pressure Ps sensor
connector.
• Check for failure in
pressure sensors Pd and
Ps.
• Check for trouble in
outdoor P.C. board (I/F).
• Check for compressor
poor compression.
Output voltage of Ps
• Check for connection
sensor is zero.
trouble involving Ps sensor
and Pd sensor connectors.
• Check connection of Ps
sensor connector.
• Check for failure in Ps
sensor.
• Check for compressor
poor compression.
• Check for failure in 4-way
valve.
• Check for failure in outdoor
P.C. board (I/F).
• Check for failure in SV4
circuit.
Output voltage of Pd sensor
• Check connection of Pd
is zero (sensor open-
sensor connector.
circuited).
• Check for failure in Pd
Pd > 4.15MPa despite
sensor.
• Check for failure in outdoor
compressor having been
turned off.
P.C. board (I/F).
Indoor P.C. board does not
• Check for failure in indoor
operate normally.
P.C. board (failure
EEPROM)
Outdoor P.C. board (I/F)
• Check power supply
does not operate normally.
voltage.
• Check power supply noise.
• Check for failure in outdoor
P.C. board (I/F).
Inverter current detection
Check power supply voltage.
circuit detects overcurrent
(AC380-415V ± 10%).
and shuts system down.
Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (Compressor).
Overcurrent is detected
• Check for failure in
several seconds after
compressor.
startup of inverter
• Check power supply voltage.
compressor.
(AC380-415V ± 10%).
• Check compressor system
wiring, particularly for open
phase.
• Check connection of
connectors/terminals on
compressor P.C. board.
• Check conductivity of case
heater.
(Check for refrigerant
problem inside
compressor.)
• Check for failure in outdoor
P.C. board (Compressor).
• Check outdoor MG-CTT.
Current flow of at least
• Check current detection
specified magnitude is
circuit wiring.
detected despite inverter
• Check failure in outdoor
P.C. board (Compressor).
compressor having been
shut turned off.