Toshiba MMY-MUP0801HT8P-TR Service Manual page 120

Air conditioner multi type, super modular multi system-u smms-u, outdoor
Table of Contents

Advertisement

<Check on the indoor unit>
(1) Display check on the remote controller (in the case of a wired remote controller)
Check that a frame, as shown in the following figure at left, is displayed on the LC display section of the
remote controller.
<RBC-AMT*>
Correct
TEMP.
FILTER
RESET
TEST
Normal status
(power supplied and operation stopped)
<RBC-ASCU11*>
Correct
If no frame is displayed, as shown in the above figure at right, the remote controller does not have a normal
supply of power; check the following items.
• Check the power supply of the indoor unit.
• Check the cabling between the indoor unit and the remote controller.
• Check whether there is a cutoff of wire around the indoor control PC board or not, and check for connection
failures of the connectors.
• Check for failure of the transformer for the indoor electrical control box.
• Check for failure of the indoor control PC board.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
SET
CL
SWING/FIX
UNIT LOUVER
Incorrect
TEMP.
TIMER SET
FILTER
RESET
TEST
SET
When power is not supplied normally
Incorrect
- 120 -
ON / OFF
FAN
MODE
TIME
SAVE
VENT
CL
SWING/FIX
UNIT LOUVER